docs: showpiece README — mermaid architecture, sensor/alert tables [#762]
Also absorbs PFVCluster operator tooling: tools/ha-ws-call.py and docs/reference-packs/ (historical, NOT loaded by HA — clearly marked). No live-config changes in this commit. Detail: https://projects.knownelement.com/issues/762
This commit is contained in:
@@ -0,0 +1,140 @@
|
||||
# REFERENCE ONLY — historical packs, NOT loaded by HA (superseded by packages/; kept for lineage). Statuses in the repo README.
|
||||
# PFV UPS + plant alert automations for Home Assistant [#439]
|
||||
#
|
||||
# Paste into automations.yaml (or via UI: paste YAML directly into the
|
||||
# automation editor). Delivery target: notify.pushover (add the Pushover
|
||||
# integration first; interim targets that exist today:
|
||||
# notify.mobile_app_ultix_sidecar / notify.mobile_app_ultix_mini /
|
||||
# notify.mobile_app_allthes_ipad).
|
||||
#
|
||||
# ENTITY IDs: created by the NUT integration when you add the two UPS config
|
||||
# entries (Settings > Devices & Services > Add Integration > Network UPS
|
||||
# Tools; hosts pfv-tsys1.knel.net and pfv-tsys9.knel.net, port 3493, user
|
||||
# homeassistant + the upsd.users password). Suggested device names:
|
||||
# "tsys1 ups" and "tsys9 ups" -> entities below. If HA names them
|
||||
# differently, check Developer Tools > States (search "_ups_status") and
|
||||
# edit the entity_id lines to match. Nothing else needs changing.
|
||||
|
||||
- alias: "PFV plant - UPS on battery"
|
||||
id: pfv_plant_ups_on_battery
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: state
|
||||
entity_id:
|
||||
- sensor.tsys1_ups_status
|
||||
- sensor.tsys9_ups_status
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{{ 'On Battery' in states(trigger.entity_id) }}
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "POWER OUTAGE"
|
||||
message: >-
|
||||
{{ state_attr(trigger.entity_id, 'friendly_name') }} lost utility
|
||||
power and is ON BATTERY at {{ states('sensor.' ~ trigger.entity_id.split('.')[1] | replace('_status', '_battery_charge')) }}% charge.
|
||||
|
||||
- alias: "PFV plant - UPS battery low"
|
||||
id: pfv_plant_ups_battery_low
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: numeric_state
|
||||
entity_id:
|
||||
- sensor.tsys1_ups_battery_charge
|
||||
- sensor.tsys9_ups_battery_charge
|
||||
below: 40
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{{ 'On Battery' in states(trigger.entity_id | replace('_battery_charge', '_status')) }}
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "UPS BATTERY LOW"
|
||||
message: >-
|
||||
{{ trigger.entity_id }} at {{ states(trigger.entity_id) }}% while on
|
||||
battery. Start graceful shutdown of VMs before hypervisors (#455 ordering).
|
||||
data:
|
||||
priority: 1
|
||||
|
||||
- alias: "PFV plant - UPS communication lost"
|
||||
id: pfv_plant_ups_comm_lost
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: state
|
||||
entity_id:
|
||||
- sensor.tsys1_ups_status
|
||||
- sensor.tsys9_ups_status
|
||||
to: unavailable
|
||||
for: "00:05:00"
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "UPS COMMS LOST"
|
||||
message: >-
|
||||
{{ trigger.entity_id }} unreachable for 5 minutes (nut-server or
|
||||
network path down; tsys1 also hosts pfv-bms itself).
|
||||
data:
|
||||
priority: 1
|
||||
|
||||
- alias: "PFV plant - utility power restored"
|
||||
id: pfv_plant_ups_power_restored
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: state
|
||||
entity_id:
|
||||
- sensor.tsys1_ups_status
|
||||
- sensor.tsys9_ups_status
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{{ trigger.from_state is not none and 'On Battery' in trigger.from_state.state
|
||||
and 'On Battery' not in states(trigger.entity_id) }}
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "Power restored"
|
||||
message: >-
|
||||
{{ state_attr(trigger.entity_id, 'friendly_name') }} is back ONLINE.
|
||||
|
||||
- alias: "PFV plant - high temperature"
|
||||
id: pfv_plant_high_temperature
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: numeric_state
|
||||
entity_id:
|
||||
- sensor.pfv_artroom_temperature
|
||||
- sensor.pfv_garage_temperature
|
||||
- sensor.pfv_tsys1_rack_temperature
|
||||
- sensor.pfv_tsys3_cpu_temperature
|
||||
- sensor.pfv_tsys4_ambient_temperature
|
||||
- sensor.pfv_tsys5_ambient_temperature
|
||||
- sensor.pfv_tsys6_cpu_temperature
|
||||
- sensor.pfv_tsys7_cpu_temperature
|
||||
- sensor.pfv_tsys9_cpu_temperature
|
||||
- sensor.pfv_jetson_temperature
|
||||
- sensor.pfv_svrpi_temperature
|
||||
- sensor.pfv_subopi3_temperature
|
||||
- sensor.pfv_subopi_dev_3_temperature
|
||||
- sensor.pfv_subopi_dev_4_temperature
|
||||
above: 104
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "HIGH TEMPERATURE"
|
||||
message: >-
|
||||
{{ trigger.entity_id }} is {{ states(trigger.entity_id) }}°F
|
||||
(threshold 104°F). Check cooling/airflow.
|
||||
data:
|
||||
priority: 1
|
||||
Reference in New Issue