docs(ups): document apcupsd test results and Energy Dashboard limitations
The APC Smart-UPS C 1500 (FW 02.2, mfg 2012) does not expose ups.load or
ups.realpower over USB HID. Tested apcupsd as an alternative — it reads the
same HID descriptor and returned COMMLOST. Debian's apcupsd package also
conflicts with nut-server (mutually exclusive).
Documented that the HA NUT integration provides battery/runtime/status sensors
only, not wattage for the Energy Dashboard. Practical path is a smart plug on
the UPS output. Updated daily-ops examples (removed ups.load reference since
the variable doesn't exist on this UPS).
NUT stack fully restored after the apcupsd test cycle.
💘 Generated with Crush
Assisted-by: Crush:glm-5.2
This commit is contained in:
+16
-5
@@ -184,8 +184,7 @@ upsc -l pfv-tsys1
|
||||
# Full variable dump for one UPS
|
||||
upsc apc-smartups-c1500@pfv-tsys1
|
||||
|
||||
# Just the live load + runtime
|
||||
upsc apc-smartups-c1500@pfv-tsys1 ups.load
|
||||
# Battery runtime (the only runtime/charge data this UPS exposes)
|
||||
upsc apc-smartups-c1500@pfv-tsys1 battery.runtime
|
||||
```
|
||||
|
||||
@@ -194,6 +193,18 @@ upsc apc-smartups-c1500@pfv-tsys1 battery.runtime
|
||||
- **No USB passthrough to the HA VM.** Keeping the UPS on the host preserves
|
||||
hypervisor graceful-shutdown capability and matches the `powerman/` pattern
|
||||
(PDU managed on the host where the adapter physically lives).
|
||||
- **Per-unit power (Watts):** `usbhid-ups` reports `ups.realpower` directly on
|
||||
the APC Smart-UPS C 1500. If absent, derive Watts as
|
||||
`load% × VA_rating × power_factor` in HA templates.
|
||||
- **No `ups.load` / `ups.realpower` on this UPS (FW 02.2, mfg 2012):** The
|
||||
APC Smart-UPS C 1500 does not expose load or power data over USB HID.
|
||||
Both NUT `usbhid-ups` and `apcupsd` (USB mode, tested 2026-07-30) read the
|
||||
same HID descriptor — the variable simply isn't there. This means the HA
|
||||
NUT integration provides **battery/runtime/status sensors only**, not
|
||||
wattage for the Energy Dashboard.
|
||||
- **apcupsd test note:** Debian's `apcupsd` package conflicts with
|
||||
`nut-server` (mutually exclusive). apcupsd USB mode returned `COMMLOST`
|
||||
even before we could check load. The APC Smart Serial protocol (serial
|
||||
cable, AP940-1524C, ~$30) DOES report load%, but this requires a serial
|
||||
port on the UPS and on the host.
|
||||
- **Energy Dashboard path:** A smart plug (Shelly Plug S / TP-Link Kasa,
|
||||
~$15-25) on the UPS output reports real watts natively and feeds the
|
||||
Energy Dashboard with zero UPS-driver hacking. The NUT sensors remain
|
||||
valuable for outage detection and graceful-shutdown automations.
|
||||
|
||||