chore: HomeAssistant ops dir (config-repo pointer, needfromcharles asks); tidy test junk [#344]
This commit is contained in:
@@ -0,0 +1,139 @@
|
||||
# PFV UPS + plant alert automations for Home Assistant [#439]
|
||||
#
|
||||
# Paste into automations.yaml (or via UI: paste YAML directly into the
|
||||
# automation editor). Delivery target: notify.pushover (add the Pushover
|
||||
# integration first; interim targets that exist today:
|
||||
# notify.mobile_app_ultix_sidecar / notify.mobile_app_ultix_mini /
|
||||
# notify.mobile_app_allthes_ipad).
|
||||
#
|
||||
# ENTITY IDs: created by the NUT integration when you add the two UPS config
|
||||
# entries (Settings > Devices & Services > Add Integration > Network UPS
|
||||
# Tools; hosts pfv-tsys1.knel.net and pfv-tsys9.knel.net, port 3493, user
|
||||
# homeassistant + the upsd.users password). Suggested device names:
|
||||
# "tsys1 ups" and "tsys9 ups" -> entities below. If HA names them
|
||||
# differently, check Developer Tools > States (search "_ups_status") and
|
||||
# edit the entity_id lines to match. Nothing else needs changing.
|
||||
|
||||
- alias: "PFV plant - UPS on battery"
|
||||
id: pfv_plant_ups_on_battery
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: state
|
||||
entity_id:
|
||||
- sensor.tsys1_ups_status
|
||||
- sensor.tsys9_ups_status
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{{ 'On Battery' in states(trigger.entity_id) }}
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "POWER OUTAGE"
|
||||
message: >-
|
||||
{{ state_attr(trigger.entity_id, 'friendly_name') }} lost utility
|
||||
power and is ON BATTERY at {{ states('sensor.' ~ trigger.entity_id.split('.')[1] | replace('_status', '_battery_charge')) }}% charge.
|
||||
|
||||
- alias: "PFV plant - UPS battery low"
|
||||
id: pfv_plant_ups_battery_low
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: numeric_state
|
||||
entity_id:
|
||||
- sensor.tsys1_ups_battery_charge
|
||||
- sensor.tsys9_ups_battery_charge
|
||||
below: 40
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{{ 'On Battery' in states(trigger.entity_id | replace('_battery_charge', '_status')) }}
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "UPS BATTERY LOW"
|
||||
message: >-
|
||||
{{ trigger.entity_id }} at {{ states(trigger.entity_id) }}% while on
|
||||
battery. Start graceful shutdown of VMs before hypervisors (#455 ordering).
|
||||
data:
|
||||
priority: 1
|
||||
|
||||
- alias: "PFV plant - UPS communication lost"
|
||||
id: pfv_plant_ups_comm_lost
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: state
|
||||
entity_id:
|
||||
- sensor.tsys1_ups_status
|
||||
- sensor.tsys9_ups_status
|
||||
to: unavailable
|
||||
for: "00:05:00"
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "UPS COMMS LOST"
|
||||
message: >-
|
||||
{{ trigger.entity_id }} unreachable for 5 minutes (nut-server or
|
||||
network path down; tsys1 also hosts pfv-bms itself).
|
||||
data:
|
||||
priority: 1
|
||||
|
||||
- alias: "PFV plant - utility power restored"
|
||||
id: pfv_plant_ups_power_restored
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: state
|
||||
entity_id:
|
||||
- sensor.tsys1_ups_status
|
||||
- sensor.tsys9_ups_status
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{{ trigger.from_state is not none and 'On Battery' in trigger.from_state.state
|
||||
and 'On Battery' not in states(trigger.entity_id) }}
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "Power restored"
|
||||
message: >-
|
||||
{{ state_attr(trigger.entity_id, 'friendly_name') }} is back ONLINE.
|
||||
|
||||
- alias: "PFV plant - high temperature"
|
||||
id: pfv_plant_high_temperature
|
||||
mode: single
|
||||
triggers:
|
||||
- trigger: numeric_state
|
||||
entity_id:
|
||||
- sensor.pfv_artroom_temperature
|
||||
- sensor.pfv_garage_temperature
|
||||
- sensor.pfv_tsys1_rack_temperature
|
||||
- sensor.pfv_tsys3_cpu_temperature
|
||||
- sensor.pfv_tsys4_ambient_temperature
|
||||
- sensor.pfv_tsys5_ambient_temperature
|
||||
- sensor.pfv_tsys6_cpu_temperature
|
||||
- sensor.pfv_tsys7_cpu_temperature
|
||||
- sensor.pfv_tsys9_cpu_temperature
|
||||
- sensor.pfv_jetson_temperature
|
||||
- sensor.pfv_svrpi_temperature
|
||||
- sensor.pfv_subopi3_temperature
|
||||
- sensor.pfv_subopi_dev_3_temperature
|
||||
- sensor.pfv_subopi_dev_4_temperature
|
||||
above: 104
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id: notify.pushover
|
||||
data:
|
||||
title: "HIGH TEMPERATURE"
|
||||
message: >-
|
||||
{{ trigger.entity_id }} is {{ states(trigger.entity_id) }}°F
|
||||
(threshold 104°F). Check cooling/airflow.
|
||||
data:
|
||||
priority: 1
|
||||
@@ -0,0 +1,62 @@
|
||||
# PFV plant energy helpers (kWh) for Home Assistant [#439]
|
||||
#
|
||||
# Paste into configuration.yaml. Riemann-sum integral: W -> kWh with the
|
||||
# `integration` sensor platform (kept across restarts). Feeds the Energy
|
||||
# dashboard (Settings > Dashboards > Energy > add grid/device consumption
|
||||
# sources pointing at these kWh sensors).
|
||||
#
|
||||
# Node power comes from the ACPI power_meter read through the SNMP extend
|
||||
# (see sensors-snmp-plant.yaml): sensor.pfv_tsys6_node_power /
|
||||
# sensor.pfv_tsys7_node_power, in watts.
|
||||
|
||||
sensor:
|
||||
- platform: integration
|
||||
source: sensor.pfv_tsys6_node_power
|
||||
name: "PFV tsys6 node energy"
|
||||
unique_id: pfv_tsys6_node_energy
|
||||
unit_prefix: k
|
||||
round: 2
|
||||
method: left
|
||||
max_sub_interval:
|
||||
minutes: 5
|
||||
|
||||
- platform: integration
|
||||
source: sensor.pfv_tsys7_node_power
|
||||
name: "PFV tsys7 node energy"
|
||||
unique_id: pfv_tsys7_node_energy
|
||||
unit_prefix: k
|
||||
round: 2
|
||||
method: left
|
||||
max_sub_interval:
|
||||
minutes: 5
|
||||
|
||||
# ---------------------------------------------------------------------------
|
||||
# UPS load -> energy (APC on tsys1, Tripp Lite on tsys9):
|
||||
# Preferred source is the NUT diagnostic sensor "Real power (W)" — enable it
|
||||
# on the NUT device page (diagnostics are disabled by default). If your UPS
|
||||
# does not expose real power, uncomment the template-watts fallback below and
|
||||
# fill in the nominal wattage from the UPS nameplate.
|
||||
#
|
||||
# - platform: integration
|
||||
# source: sensor.tsys1_ups_watts
|
||||
# name: "PFV tsys1 UPS energy"
|
||||
# unique_id: pfv_tsys1_ups_energy
|
||||
# unit_prefix: k
|
||||
# round: 2
|
||||
# method: left
|
||||
# max_sub_interval:
|
||||
# minutes: 5
|
||||
#
|
||||
# Fallback template (only if no realpower diagnostic entity exists):
|
||||
#
|
||||
# template:
|
||||
# - sensor:
|
||||
# - name: "PFV tsys1 UPS watts"
|
||||
# unique_id: pfv_tsys1_ups_watts
|
||||
# unit_of_measurement: "W"
|
||||
# device_class: power
|
||||
# state_class: measurement
|
||||
# state: >-
|
||||
# {{ (states('sensor.tsys1_ups_load') | float(0)
|
||||
# * NOMINAL_WATTS / 100) | round(0) }}
|
||||
# ---------------------------------------------------------------------------
|
||||
@@ -0,0 +1,292 @@
|
||||
# PFV physical-plant SNMP sensors for Home Assistant [#439]
|
||||
#
|
||||
# Paste the sensor block below into pfv-bms configuration.yaml (or an
|
||||
# !include). All temperatures are converted C to F at the display layer per
|
||||
# founder ruling 2026-08-27 (transport stays lm-sensors format, °C).
|
||||
#
|
||||
# Source: lmsensors-extend snmpd extend, deployed on all 7 Proxmox hosts +
|
||||
# stlpc-artroom + stlpc-garage (see dcinfra/sensors/temper/).
|
||||
# Extend OID: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
#
|
||||
# Hosts resolve via knel.net DNS from pfv-bms (verify in Developer Tools >
|
||||
# States after reload; if a host shows 'unknown' check DNS + the snmpd
|
||||
# source ACL which already includes the pfv-bms LAN IP 192.168.3.12).
|
||||
#
|
||||
# Per founder ruling (#343): LibreNMS does NOT graph temperatures; these HA
|
||||
# sensors are the canonical environmental record for the plant.
|
||||
|
||||
sensor:
|
||||
# --- TEMPer USB probe hosts (External probe, Internal fallback) ---
|
||||
- platform: snmp
|
||||
name: "PFV artroom temperature"
|
||||
host: stlpc-artroom.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_artroom_temperature
|
||||
value_template: >-
|
||||
{% set ext = value | regex_findall('External:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{% set int = value | regex_findall('Internal:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{% set c = (ext | first) if ext else ((int | first) if int else none) %}
|
||||
{{ ((c | float * 9 / 5) + 32) | round(1) if c is not none else 'unknown' }}
|
||||
|
||||
- platform: snmp
|
||||
name: "PFV garage temperature"
|
||||
host: stlpc-garage.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_garage_temperature
|
||||
value_template: >-
|
||||
{% set ext = value | regex_findall('External:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{% set int = value | regex_findall('Internal:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{% set c = (ext | first) if ext else ((int | first) if int else none) %}
|
||||
{{ ((c | float * 9 / 5) + 32) | round(1) if c is not none else 'unknown' }}
|
||||
|
||||
- platform: snmp
|
||||
name: "PFV tsys1 rack temperature"
|
||||
host: pfv-tsys1.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_tsys1_rack_temperature
|
||||
value_template: >-
|
||||
{% set ext = value | regex_findall('External:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{% set int = value | regex_findall('Internal:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{% set c = (ext | first) if ext else ((int | first) if int else none) %}
|
||||
{{ ((c | float * 9 / 5) + 32) | round(1) if c is not none else 'unknown' }}
|
||||
|
||||
# --- Native lm-sensors hosts (label picked per host ground truth 2026-08-27) ---
|
||||
# tsys3 Precision 7510: CPU package
|
||||
- platform: snmp
|
||||
name: "PFV tsys3 CPU temperature"
|
||||
host: pfv-tsys3.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_tsys3_cpu_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('Package id 0:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
# tsys4 Precision T1700: Dell SMM ambient (board inlet)
|
||||
- platform: snmp
|
||||
name: "PFV tsys4 ambient temperature"
|
||||
host: pfv-tsys4.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_tsys4_ambient_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('Ambient:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
# tsys5 Precision T7500: Dell SMM ambient (board inlet)
|
||||
- platform: snmp
|
||||
name: "PFV tsys5 ambient temperature"
|
||||
host: pfv-tsys5.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_tsys5_ambient_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('Ambient:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
# tsys6 PowerEdge R610: socket-0 core temp (no Package label on Westmere)
|
||||
- platform: snmp
|
||||
name: "PFV tsys6 CPU temperature"
|
||||
host: pfv-tsys6.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_tsys6_cpu_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('Core 0:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
# tsys6 ACPI power meter (node draw, watts)
|
||||
- platform: snmp
|
||||
name: "PFV tsys6 node power"
|
||||
host: pfv-tsys6.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: power
|
||||
state_class: measurement
|
||||
unit_of_measurement: "W"
|
||||
unique_id: pfv_tsys6_node_power
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('power1:\s*(\d+\.?\d*)\s*W') %}
|
||||
{{ m | first | float if m else 'unknown' }}
|
||||
|
||||
# tsys7 PowerEdge R620: package temp
|
||||
- platform: snmp
|
||||
name: "PFV tsys7 CPU temperature"
|
||||
host: pfv-tsys7.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_tsys7_cpu_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('Package id 0:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
# tsys7 ACPI power meter (node draw, watts)
|
||||
- platform: snmp
|
||||
name: "PFV tsys7 node power"
|
||||
host: pfv-tsys7.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: power
|
||||
state_class: measurement
|
||||
unit_of_measurement: "W"
|
||||
unique_id: pfv_tsys7_node_power
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('power1:\s*(\d+\.?\d*)\s*W') %}
|
||||
{{ m | first | float if m else 'unknown' }}
|
||||
|
||||
# tsys9 OptiPlex 7080: package temp
|
||||
- platform: snmp
|
||||
name: "PFV tsys9 CPU temperature"
|
||||
host: pfv-tsys9.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_tsys9_cpu_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('Package id 0:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
# --- SBC fleet (sysfs thermal fallback in lmsensors-extend v2; temp1 = zone0/SoC) ---
|
||||
- platform: snmp
|
||||
name: "PFV jetson temperature"
|
||||
host: pfv-jetson-nano-1.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_jetson_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
- platform: snmp
|
||||
name: "PFV svrpi temperature"
|
||||
host: pfvsvrpi.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_svrpi_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
- platform: snmp
|
||||
name: "PFV subopi3 temperature"
|
||||
host: subopi3.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_subopi3_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
- platform: snmp
|
||||
name: "PFV subopi-dev-3 temperature"
|
||||
host: subopi-dev-3.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_subopi_dev_3_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
- platform: snmp
|
||||
name: "PFV subopi-dev-4 temperature"
|
||||
host: subopi-dev-4.knel.net
|
||||
version: 2c
|
||||
community: kn3lmgmt
|
||||
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
|
||||
accept_errors: true
|
||||
device_class: temperature
|
||||
state_class: measurement
|
||||
unit_of_measurement: "°F"
|
||||
unique_id: pfv_subopi_dev_4_temperature
|
||||
value_template: >-
|
||||
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
|
||||
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
|
||||
|
||||
# ---------------------------------------------------------------------------
|
||||
# PLACEHOLDERS — enable after dependencies land (do not invent OIDs live):
|
||||
#
|
||||
# Garage PDU (AP7830, SNMPv1, HA owns PDU power graphing per #343 ruling):
|
||||
# Needs the custom v1 community from LibreNMS (founder: supply value as a
|
||||
# HA secret) + OID discovery via snmpwalk of .1.3.6.1.4.1.318 subtree.
|
||||
# - platform: snmp
|
||||
# name: "PFV garage PDU current"
|
||||
# host: <pdu-dns-name>
|
||||
# version: 1
|
||||
# community: !secret pdu_community
|
||||
# baseoid: <discover: bank current OID>
|
||||
#
|
||||
# iDRAC6 feeds (pfv-tsys6-oob / pfv-tsys7-oob, community kn3lmgmt) once the
|
||||
# OOB ports are cabled (#460): inlet temp + system power via Dell PowerNet
|
||||
# MIB. OIDs to be walked and pinned post-cabling.
|
||||
# ---------------------------------------------------------------------------
|
||||
Reference in New Issue
Block a user