fix(automations): drop invalid nested data: blocks breaking 3 plant alarms [#344]

notify.send_message rejects extra data['data'] (old mobile-app push
syntax) — UPS battery low, UPS comm lost, and high-temperature alerts
all errored on every fire. Blocks removed; notifications send plain.

https://projects.knownelement.com/issues/344
This commit is contained in:
2026-09-02 20:44:10 -05:00
parent f1898daa8a
commit cdc270f8e8
-6
View File
@@ -41,8 +41,6 @@
title: UPS BATTERY LOW title: UPS BATTERY LOW
message: '{{ trigger.entity_id }} at {{ states(trigger.entity_id) }}% while message: '{{ trigger.entity_id }} at {{ states(trigger.entity_id) }}% while
on battery. Start graceful shutdown of VMs before hypervisors (#455 ordering).' on battery. Start graceful shutdown of VMs before hypervisors (#455 ordering).'
data:
priority: 1
mode: single mode: single
- id: pfv_plant_ups_comm_lost - id: pfv_plant_ups_comm_lost
alias: PFV plant - UPS communication lost alias: PFV plant - UPS communication lost
@@ -63,8 +61,6 @@
title: UPS COMMS LOST title: UPS COMMS LOST
message: '{{ trigger.entity_id }} unreachable for 5 minutes (nut-server or network message: '{{ trigger.entity_id }} unreachable for 5 minutes (nut-server or network
path down; tsys1 also hosts pfv-bms itself).' path down; tsys1 also hosts pfv-bms itself).'
data:
priority: 1
mode: single mode: single
- id: pfv_plant_ups_power_restored - id: pfv_plant_ups_power_restored
alias: PFV plant - utility power restored alias: PFV plant - utility power restored
@@ -122,8 +118,6 @@
title: HIGH TEMPERATURE title: HIGH TEMPERATURE
message: '{{ trigger.entity_id }} is {{ states(trigger.entity_id) }}°F (threshold message: '{{ trigger.entity_id }} is {{ states(trigger.entity_id) }}°F (threshold
104°F). Check cooling/airflow.' 104°F). Check cooling/airflow.'
data:
priority: 1
mode: single mode: single
- id: pfv_plant_sensor_watchdog - id: pfv_plant_sensor_watchdog
alias: PFV plant - sensor watchdog (unavailable sensors) alias: PFV plant - sensor watchdog (unavailable sensors)