docs: showpiece README — mermaid architecture, sensor/alert tables [#762]

Also absorbs PFVCluster operator tooling: tools/ha-ws-call.py and
docs/reference-packs/ (historical, NOT loaded by HA — clearly marked).
No live-config changes in this commit.

Detail: https://projects.knownelement.com/issues/762
This commit is contained in:
2026-09-03 13:34:53 -05:00
parent 96e70aa231
commit 6c5efbb609
5 changed files with 699 additions and 31 deletions
+150 -31
View File
@@ -1,45 +1,164 @@
# pfv-bms — Home Assistant configuration (Turnsys PFV) # 🏠 pfv-bms — the house brain
Production Home Assistant configuration for a private residence + > **Datacenter-grade monitoring and access control for a private residence + server room** —
server room: physical-plant environmental monitoring (temperatures, > 372 entities, ~260 sensors, and a badge-actuated door, all deployed by `git push`.
power, UPS), server-room badge access control, and alerting.
Licensed under the [GNU AGPLv3](LICENSE) — see [AGPL compliance ![license](https://img.shields.io/badge/license-AGPLv3-blue)
notes](#license) below. ![HA](https://img.shields.io/badge/Home%20Assistant-2026.8.3-41bdf5?logo=homeassistant&logoColor=white)
![HAOS](https://img.shields.io/badge/HAOS-18.2-orange)
![deploy](https://img.shields.io/badge/deploy-git%20push%20%E2%86%92%20live-4EAA25)
![entities](https://img.shields.io/badge/entities-372-9c27b0)
## What lives here Production Home Assistant configuration for the Turnsys PFV —
environmental monitoring (temperatures, power, UPS) across a seven-node
Proxmox fleet plus single-board computers, server-room badge access
control, and tiered alerting to mobile devices.
- `configuration.yaml` + `packages/` — the full running config, Work tracking: [Redmine](https://projects.knownelement.com)
deployed to the HAOS box via a git-webhook pipeline ([#344](https://projects.knownelement.com/issues/344) umbrella) ·
- `packages/doorman.yaml` — badge-scan ingest + whitelist decisions Docs: [VP TechOps on Discourse](https://community.turnsys.com/c/vp-techops)
(server-room door access)
- `packages/plant_snmp.yaml` — fleet temperature/power sensors over
SNMP (lm-sensors extends, iDRAC, UPS, PDU relay)
- `automations.yaml` — tiered thermal alerts + sensor watchdogs
- `dashboards/` — Lovelace dashboards
## Security model (read this before forking) ---
## 🗺️ System architecture
```mermaid
flowchart LR
subgraph FIELD[📡 The field]
TS[🖥️ 7× Proxmox hosts<br/>lm-sensors + iDRAC extends]
BOARDS[🥧 SBCs<br/>pfvsvrpi · jetson · 3× subopi]
UPS[🔋 UPS on tsys1<br/>NUT server :3493]
PDU[🔌 Garage PDU<br/>SNMPv1 relay]
METER[⚡ Utility meter<br/>Smart Meter Texas]
READER[🪪 Badge readers<br/>pfvsvrpi · ultix-field]
end
subgraph HA[🏠 pfv-bms — this repo]
INGEST[📦 packages/plant_snmp.yaml<br/>SNMP pollers → raw sensors]
TEMPLATE[🧮 template sensors<br/>raw → °F/units + thresholds]
DOOR[🚪 packages/doorman.yaml<br/>scan ingest + decision engine]
ROSTER[🔒 roster sensors<br/>REST poll of private access-roster]
ENERGY[📊 utility_meter +<br/>Riemann-sum energy]
AUTO[🚨 automations.yaml<br/>tiered thermal + UPS alerts]
end
subgraph OUT[📲 Outcomes]
ALERT[📱 push alerts<br/>companion apps]
LOG[📓 logbook + history<br/>every scan, every degree]
DASH[🖥️ dashboards<br/>server-room + plant]
RELAY[⚡ doorctl → usbrelay<br/>→ door strike]
end
READER -->|webhook| DOOR
DOOR -->|whitelist| ROSTER
DOOR -->|armed + valid| RELAY
TS & BOARDS -->|SNMP| INGEST
UPS -->|NUT| INGEST
PDU -->|SNMP relay| INGEST
METER -->|REST| INGEST
INGEST --> TEMPLATE --> AUTO
INGEST --> ENERGY
AUTO --> ALERT
TEMPLATE & DOOR --> LOG & DASH
```
### 🛡️ Badge access lane (server-room door)
| Component | Role | Lives |
|-----------|------|-------|
| USB HID readers | 13.56 MHz badge readers (keyboard-emulating) | door + dev bench |
| [`KNEL/doorman`](https://git.knownelement.com/KNEL/doorman) | pure-bash listener, decode, webhook, doorctl | `pfvsvrpi` (prod), `ultix-field` (dev) |
| `packages/doorman.yaml` | scan ingest, whitelist decision, alerts, unlock dispatch | **this repo** |
| [`KNEL/access-roster`](https://git.knownelement.com/KNEL/access-roster) 🔒 | badge IDs + holders — **private**, two-human PR gate | gitea (private) |
| `doorctl` + usbrelay | socket-activated, token + source-IP ACL, EXIT-trap secured | `pfvsvrpi` |
Fail-closed end to end: HA unreachable → the door does not open.
Break-glass badges fire the relay locally (works with HA down) and
report `local_unlock` so HA never double-fires. Arm switch
(`input_boolean.doorman_unlock_enabled`) is founder-level control.
Verified end-to-end 2026-09-03: real armed scan → dispatch → relay.
---
## 🌡️ Environmental monitoring
Raw SNMP pollers (`packages/plant_snmp.yaml`) → unit-normalized
template sensors → tiered automations. Every host contributes
lm-sensors extends; iDRAC hosts add inlet/exhaust/CPU; NUT feeds UPS
electricals.
| Family | Coverage |
|--------|----------|
| 🖥️ Host silicon | CPU/drive/NVMe/PCH temps on 7 Proxmox hosts |
| 🌡️ Thermal zones | rack ambient, DIMM banks, GPU, tsys7 iDRAC inlet→exhaust ΔT |
| 🥧 Boards | pfvsvrpi, jetson, 3× subopi |
| 🔋 UPS | tsys1 battery charge/voltage, on-battery + runtime alerts |
| ⚡ Power | whole-house kWh (utility), tsys6/7 node watts + kWh integrals, garage PDU amps |
| 🏠 Rooms | temp/humidity/battery sensors (Govee, cloud-fed) |
### 🚨 Alert tiers (automations.yaml)
| Trigger | Threshold |
|---------|-----------|
| Drive / DIMM temps | > 140 °F |
| NVMe | > 150 °F |
| PCH | > 160 °F |
| GPU | > 185 °F |
| Ambient | > 104 °F |
| UPS | on-battery transitions + runtime |
| Watchdog | plant sensor freshness sweep every 30 min |
### 📊 Snapshot (2026-09-03)
372 entities · ~260 sensors · 45 temperature sensors · 21
electrical/energy sensors · 8 todo lists · 2-way alerting to companion
apps.
---
## 🔐 Security model (read this before forking)
- **No secrets in git, ever.** Everything sensitive is `!secret` - **No secrets in git, ever.** Everything sensitive is `!secret`
indirection into an on-box `secrets.yaml` (gitignored). Verified by indirection into an on-box `secrets.yaml` (gitignored). Verified by
full-history scans. full-history scans.
- **Badge IDs are NOT in this repo.** The badge roster lives in a - **Badge IDs are NOT in this repo.** The roster lives in the *private*
separate *private* repository (`access-roster`, two-human PR gate) [`KNEL/access-roster`](https://git.knownelement.com/KNEL/access-roster)
and is fetched live at runtime via the gitea API with a secret auth repo (two-human PR gate) and is fetched live at runtime.
header. This repo contains only the decision logic. - **Fail-closed access control** — see the badge lane above.
- Battery-powered room sensors and lock integrations are cloud-fed; - Battery room sensors and locks are cloud-fed; credentials also live
their credentials also live in `secrets.yaml`. in `secrets.yaml`.
## Related ## 🚀 Deployment pipeline
- Work tracking: [Redmine project 55](https://projects.knownelement.com) ```mermaid
([#344](https://projects.knownelement.com/issues/344) HA integration, flowchart LR
[#345](https://projects.knownelement.com/issues/345) badge access, PUSH[📝 git push] --> HOOK[gitea webhook<br/>fast path]
[#762](https://projects.knownelement.com/issues/762) publication) PUSH --> SHA[sha-watch<br/>safety net · 300 s poll]
- Documentation: HOOK & SHA --> CHECK{changed files?}
[VP TechOps on Discourse](https://community.turnsys.com/c/vp-techops) CHECK -->|packages/**| RESTART[♻️ core restart<br/>webhook triggers need it]
- Badge listener/relay code: [KNEL/doorman](https://git.knownelement.com/KNEL/doorman) CHECK -->|other YAML| RELOAD[⚡ reload only<br/>~5 min to live]
- Wider fleet (Proxmox, DNS, monitoring): [KNEL/PFVCluster](https://git.knownelement.com/KNEL/PFVCluster) ```
Gate before pushing `packages/**`: `ha core check` must pass on-box.
Measured end-to-end: 4 m 52 s commit → live.
## 🗺️ Repo map
| Path | What |
|------|------|
| `configuration.yaml` | entrypoint + package includes |
| `packages/doorman.yaml` | 🚪 badge scan ingest + decisions |
| `packages/plant_snmp.yaml` | 🌡️ SNMP pollers + templates |
| `automations.yaml` | 🚨 tiered alerts + watchdogs |
| `dashboards/` | Lovelace dashboards |
| `tools/` | operator tooling (websocket CLI) |
| `docs/reference-packs/` | historical YAML references — NOT loaded |
## 🔗 Related
- Badge listener + relay code: [`KNEL/doorman`](https://git.knownelement.com/KNEL/doorman)
- Wider fleet (Proxmox, DNS, monitoring): [`KNEL/PFVCluster`](https://git.knownelement.com/KNEL/PFVCluster)
- Badge roster (private): `KNEL/access-roster` 🔒
## License ## License
@@ -0,0 +1,140 @@
# REFERENCE ONLY — historical packs, NOT loaded by HA (superseded by packages/; kept for lineage). Statuses in the repo README.
# PFV UPS + plant alert automations for Home Assistant [#439]
#
# Paste into automations.yaml (or via UI: paste YAML directly into the
# automation editor). Delivery target: notify.pushover (add the Pushover
# integration first; interim targets that exist today:
# notify.mobile_app_ultix_sidecar / notify.mobile_app_ultix_mini /
# notify.mobile_app_allthes_ipad).
#
# ENTITY IDs: created by the NUT integration when you add the two UPS config
# entries (Settings > Devices & Services > Add Integration > Network UPS
# Tools; hosts pfv-tsys1.knel.net and pfv-tsys9.knel.net, port 3493, user
# homeassistant + the upsd.users password). Suggested device names:
# "tsys1 ups" and "tsys9 ups" -> entities below. If HA names them
# differently, check Developer Tools > States (search "_ups_status") and
# edit the entity_id lines to match. Nothing else needs changing.
- alias: "PFV plant - UPS on battery"
id: pfv_plant_ups_on_battery
mode: single
triggers:
- trigger: state
entity_id:
- sensor.tsys1_ups_status
- sensor.tsys9_ups_status
conditions:
- condition: template
value_template: >-
{{ 'On Battery' in states(trigger.entity_id) }}
actions:
- action: notify.send_message
target:
entity_id: notify.pushover
data:
title: "POWER OUTAGE"
message: >-
{{ state_attr(trigger.entity_id, 'friendly_name') }} lost utility
power and is ON BATTERY at {{ states('sensor.' ~ trigger.entity_id.split('.')[1] | replace('_status', '_battery_charge')) }}% charge.
- alias: "PFV plant - UPS battery low"
id: pfv_plant_ups_battery_low
mode: single
triggers:
- trigger: numeric_state
entity_id:
- sensor.tsys1_ups_battery_charge
- sensor.tsys9_ups_battery_charge
below: 40
conditions:
- condition: template
value_template: >-
{{ 'On Battery' in states(trigger.entity_id | replace('_battery_charge', '_status')) }}
actions:
- action: notify.send_message
target:
entity_id: notify.pushover
data:
title: "UPS BATTERY LOW"
message: >-
{{ trigger.entity_id }} at {{ states(trigger.entity_id) }}% while on
battery. Start graceful shutdown of VMs before hypervisors (#455 ordering).
data:
priority: 1
- alias: "PFV plant - UPS communication lost"
id: pfv_plant_ups_comm_lost
mode: single
triggers:
- trigger: state
entity_id:
- sensor.tsys1_ups_status
- sensor.tsys9_ups_status
to: unavailable
for: "00:05:00"
actions:
- action: notify.send_message
target:
entity_id: notify.pushover
data:
title: "UPS COMMS LOST"
message: >-
{{ trigger.entity_id }} unreachable for 5 minutes (nut-server or
network path down; tsys1 also hosts pfv-bms itself).
data:
priority: 1
- alias: "PFV plant - utility power restored"
id: pfv_plant_ups_power_restored
mode: single
triggers:
- trigger: state
entity_id:
- sensor.tsys1_ups_status
- sensor.tsys9_ups_status
conditions:
- condition: template
value_template: >-
{{ trigger.from_state is not none and 'On Battery' in trigger.from_state.state
and 'On Battery' not in states(trigger.entity_id) }}
actions:
- action: notify.send_message
target:
entity_id: notify.pushover
data:
title: "Power restored"
message: >-
{{ state_attr(trigger.entity_id, 'friendly_name') }} is back ONLINE.
- alias: "PFV plant - high temperature"
id: pfv_plant_high_temperature
mode: single
triggers:
- trigger: numeric_state
entity_id:
- sensor.pfv_artroom_temperature
- sensor.pfv_garage_temperature
- sensor.pfv_tsys1_rack_temperature
- sensor.pfv_tsys3_cpu_temperature
- sensor.pfv_tsys4_ambient_temperature
- sensor.pfv_tsys5_ambient_temperature
- sensor.pfv_tsys6_cpu_temperature
- sensor.pfv_tsys7_cpu_temperature
- sensor.pfv_tsys9_cpu_temperature
- sensor.pfv_jetson_temperature
- sensor.pfv_svrpi_temperature
- sensor.pfv_subopi3_temperature
- sensor.pfv_subopi_dev_3_temperature
- sensor.pfv_subopi_dev_4_temperature
above: 104
actions:
- action: notify.send_message
target:
entity_id: notify.pushover
data:
title: "HIGH TEMPERATURE"
message: >-
{{ trigger.entity_id }} is {{ states(trigger.entity_id) }}°F
(threshold 104°F). Check cooling/airflow.
data:
priority: 1
@@ -0,0 +1,63 @@
# REFERENCE ONLY — historical packs, NOT loaded by HA (superseded by packages/; kept for lineage). Statuses in the repo README.
# PFV plant energy helpers (kWh) for Home Assistant [#439]
#
# Paste into configuration.yaml. Riemann-sum integral: W -> kWh with the
# `integration` sensor platform (kept across restarts). Feeds the Energy
# dashboard (Settings > Dashboards > Energy > add grid/device consumption
# sources pointing at these kWh sensors).
#
# Node power comes from the ACPI power_meter read through the SNMP extend
# (see sensors-snmp-plant.yaml): sensor.pfv_tsys6_node_power /
# sensor.pfv_tsys7_node_power, in watts.
sensor:
- platform: integration
source: sensor.pfv_tsys6_node_power
name: "PFV tsys6 node energy"
unique_id: pfv_tsys6_node_energy
unit_prefix: k
round: 2
method: left
max_sub_interval:
minutes: 5
- platform: integration
source: sensor.pfv_tsys7_node_power
name: "PFV tsys7 node energy"
unique_id: pfv_tsys7_node_energy
unit_prefix: k
round: 2
method: left
max_sub_interval:
minutes: 5
# ---------------------------------------------------------------------------
# UPS load -> energy (APC on tsys1, Tripp Lite on tsys9):
# Preferred source is the NUT diagnostic sensor "Real power (W)" — enable it
# on the NUT device page (diagnostics are disabled by default). If your UPS
# does not expose real power, uncomment the template-watts fallback below and
# fill in the nominal wattage from the UPS nameplate.
#
# - platform: integration
# source: sensor.tsys1_ups_watts
# name: "PFV tsys1 UPS energy"
# unique_id: pfv_tsys1_ups_energy
# unit_prefix: k
# round: 2
# method: left
# max_sub_interval:
# minutes: 5
#
# Fallback template (only if no realpower diagnostic entity exists):
#
# template:
# - sensor:
# - name: "PFV tsys1 UPS watts"
# unique_id: pfv_tsys1_ups_watts
# unit_of_measurement: "W"
# device_class: power
# state_class: measurement
# state: >-
# {{ (states('sensor.tsys1_ups_load') | float(0)
# * NOMINAL_WATTS / 100) | round(0) }}
# ---------------------------------------------------------------------------
@@ -0,0 +1,293 @@
# REFERENCE ONLY — historical packs, NOT loaded by HA (superseded by packages/; kept for lineage). Statuses in the repo README.
# PFV physical-plant SNMP sensors for Home Assistant [#439]
#
# Paste the sensor block below into pfv-bms configuration.yaml (or an
# !include). All temperatures are converted C to F at the display layer per
# founder ruling 2026-08-27 (transport stays lm-sensors format, °C).
#
# Source: lmsensors-extend snmpd extend, deployed on all 7 Proxmox hosts +
# stlpc-artroom + stlpc-garage (see dcinfra/sensors/temper/).
# Extend OID: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
#
# Hosts resolve via knel.net DNS from pfv-bms (verify in Developer Tools >
# States after reload; if a host shows 'unknown' check DNS + the snmpd
# source ACL which already includes the pfv-bms LAN IP 192.168.3.12).
#
# Per founder ruling (#343): LibreNMS does NOT graph temperatures; these HA
# sensors are the canonical environmental record for the plant.
sensor:
# --- TEMPer USB probe hosts (External probe, Internal fallback) ---
- platform: snmp
name: "PFV artroom temperature"
host: stlpc-artroom.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_artroom_temperature
value_template: >-
{% set ext = value | regex_findall('External:\s*\+?(-?\d+\.?\d*)') %}
{% set int = value | regex_findall('Internal:\s*\+?(-?\d+\.?\d*)') %}
{% set c = (ext | first) if ext else ((int | first) if int else none) %}
{{ ((c | float * 9 / 5) + 32) | round(1) if c is not none else 'unknown' }}
- platform: snmp
name: "PFV garage temperature"
host: stlpc-garage.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_garage_temperature
value_template: >-
{% set ext = value | regex_findall('External:\s*\+?(-?\d+\.?\d*)') %}
{% set int = value | regex_findall('Internal:\s*\+?(-?\d+\.?\d*)') %}
{% set c = (ext | first) if ext else ((int | first) if int else none) %}
{{ ((c | float * 9 / 5) + 32) | round(1) if c is not none else 'unknown' }}
- platform: snmp
name: "PFV tsys1 rack temperature"
host: pfv-tsys1.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_tsys1_rack_temperature
value_template: >-
{% set ext = value | regex_findall('External:\s*\+?(-?\d+\.?\d*)') %}
{% set int = value | regex_findall('Internal:\s*\+?(-?\d+\.?\d*)') %}
{% set c = (ext | first) if ext else ((int | first) if int else none) %}
{{ ((c | float * 9 / 5) + 32) | round(1) if c is not none else 'unknown' }}
# --- Native lm-sensors hosts (label picked per host ground truth 2026-08-27) ---
# tsys3 Precision 7510: CPU package
- platform: snmp
name: "PFV tsys3 CPU temperature"
host: pfv-tsys3.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_tsys3_cpu_temperature
value_template: >-
{% set m = value | regex_findall('Package id 0:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
# tsys4 Precision T1700: Dell SMM ambient (board inlet)
- platform: snmp
name: "PFV tsys4 ambient temperature"
host: pfv-tsys4.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_tsys4_ambient_temperature
value_template: >-
{% set m = value | regex_findall('Ambient:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
# tsys5 Precision T7500: Dell SMM ambient (board inlet)
- platform: snmp
name: "PFV tsys5 ambient temperature"
host: pfv-tsys5.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_tsys5_ambient_temperature
value_template: >-
{% set m = value | regex_findall('Ambient:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
# tsys6 PowerEdge R610: socket-0 core temp (no Package label on Westmere)
- platform: snmp
name: "PFV tsys6 CPU temperature"
host: pfv-tsys6.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_tsys6_cpu_temperature
value_template: >-
{% set m = value | regex_findall('Core 0:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
# tsys6 ACPI power meter (node draw, watts)
- platform: snmp
name: "PFV tsys6 node power"
host: pfv-tsys6.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: power
state_class: measurement
unit_of_measurement: "W"
unique_id: pfv_tsys6_node_power
value_template: >-
{% set m = value | regex_findall('power1:\s*(\d+\.?\d*)\s*W') %}
{{ m | first | float if m else 'unknown' }}
# tsys7 PowerEdge R620: package temp
- platform: snmp
name: "PFV tsys7 CPU temperature"
host: pfv-tsys7.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_tsys7_cpu_temperature
value_template: >-
{% set m = value | regex_findall('Package id 0:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
# tsys7 ACPI power meter (node draw, watts)
- platform: snmp
name: "PFV tsys7 node power"
host: pfv-tsys7.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: power
state_class: measurement
unit_of_measurement: "W"
unique_id: pfv_tsys7_node_power
value_template: >-
{% set m = value | regex_findall('power1:\s*(\d+\.?\d*)\s*W') %}
{{ m | first | float if m else 'unknown' }}
# tsys9 OptiPlex 7080: package temp
- platform: snmp
name: "PFV tsys9 CPU temperature"
host: pfv-tsys9.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_tsys9_cpu_temperature
value_template: >-
{% set m = value | regex_findall('Package id 0:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
# --- SBC fleet (sysfs thermal fallback in lmsensors-extend v2; temp1 = zone0/SoC) ---
- platform: snmp
name: "PFV jetson temperature"
host: pfv-jetson-nano-1.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_jetson_temperature
value_template: >-
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
- platform: snmp
name: "PFV svrpi temperature"
host: pfvsvrpi.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_svrpi_temperature
value_template: >-
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
- platform: snmp
name: "PFV subopi3 temperature"
host: subopi3.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_subopi3_temperature
value_template: >-
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
- platform: snmp
name: "PFV subopi-dev-3 temperature"
host: subopi-dev-3.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_subopi_dev_3_temperature
value_template: >-
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
- platform: snmp
name: "PFV subopi-dev-4 temperature"
host: subopi-dev-4.knel.net
version: 2c
community: kn3lmgmt
baseoid: .1.3.6.1.4.1.8072.1.3.2.3.1.2.9.108.109.115.101.110.115.111.114.115
accept_errors: true
device_class: temperature
state_class: measurement
unit_of_measurement: "°F"
unique_id: pfv_subopi_dev_4_temperature
value_template: >-
{% set m = value | regex_findall('temp1:\s*\+?(-?\d+\.?\d*)') %}
{{ ((m | first | float * 9 / 5) + 32) | round(1) if m else 'unknown' }}
# ---------------------------------------------------------------------------
# PLACEHOLDERS — enable after dependencies land (do not invent OIDs live):
#
# Garage PDU (AP7830, SNMPv1, HA owns PDU power graphing per #343 ruling):
# Needs the custom v1 community from LibreNMS (founder: supply value as a
# HA secret) + OID discovery via snmpwalk of .1.3.6.1.4.1.318 subtree.
# - platform: snmp
# name: "PFV garage PDU current"
# host: <pdu-dns-name>
# version: 1
# community: !secret pdu_community
# baseoid: <discover: bank current OID>
#
# iDRAC6 feeds (pfv-tsys6-oob / pfv-tsys7-oob, community kn3lmgmt) once the
# OOB ports are cabled (#460): inlet temp + system power via Dell PowerNet
# MIB. OIDs to be walked and pinned post-cabling.
# ---------------------------------------------------------------------------
+53
View File
@@ -0,0 +1,53 @@
#!/usr/bin/env python3
"""ha-ws-call: send websocket commands to Home Assistant, print JSON replies.
Env: HASS_URL (http(s)://host[:port]), HASS_TOKEN (long-lived token).
Args: one or more JSON command objects — argv literals or file paths.
Replies printed one-per-command, JSON indented. Stdlib + websockets only.
Usage example (docker, from repo root):
docker run --rm --network host --env-file ~/.creds/homeassistant.env \
-v "$PWD/HomeAssistant:/w" python:3.12-alpine \
sh -c 'pip install -q websockets && python /w/ha-ws-call.py "{...json...}"'
"""
import asyncio
import json
import os
import sys
try:
import websockets
except ImportError:
sys.exit("missing dependency: pip install websockets")
def load_cmd(arg):
if arg.startswith("{"):
return json.loads(arg)
with open(arg, encoding="latin1") as handle:
return json.load(handle)
async def main():
base = os.environ["HASS_URL"]
url = base.replace("http", "ws", 1).rstrip("/") + "/api/websocket"
token = os.environ["HASS_TOKEN"]
cmds = [load_cmd(arg) for arg in sys.argv[1:]]
async with websockets.connect(url, max_size=16 * 1024 * 1024) as ws:
hello = json.loads(await ws.recv())
if hello.get("type") != "auth_required":
sys.exit(f"unexpected hello: {hello}")
await ws.send(json.dumps({"type": "auth", "access_token": token}))
authed = json.loads(await ws.recv())
if authed.get("type") != "auth_ok":
sys.exit(f"auth failed: {authed}")
for message_id, cmd in enumerate(cmds, start=1):
cmd = dict(cmd)
cmd["id"] = message_id
await ws.send(json.dumps(cmd))
reply = json.loads(await ws.recv())
print(json.dumps(reply, indent=1))
if __name__ == "__main__":
asyncio.run(main())