From ec974c906109813d7a4f1d9768389fda9863fd96 Mon Sep 17 00:00:00 2001 From: reachableceo Date: Wed, 2 Sep 2026 23:17:07 -0500 Subject: [PATCH] fix(alarms): CPU/SoC silicon tier at 176F - ambient 104F only for true ambient [#733] subopi3 SoC idles at 117F and false-alarmed the 104F ambient bucket at 23:15 CDT. Silicon (server CPUs, drac cpu, Pi/Jetson SoCs) now alerts at 176F (80C pre-throttle). Detail: https://projects.knownelement.com/issues/733 --- automations.yaml | 20 +++++++++++++------- 1 file changed, 13 insertions(+), 7 deletions(-) diff --git a/automations.yaml b/automations.yaml index 2629f16..5d61ed9 100644 --- a/automations.yaml +++ b/automations.yaml @@ -142,27 +142,33 @@ - sensor.pfv_tsys3_pch_temperature - sensor.pfv_tsys9_pch_temperature above: 160 + # CPU-SoC silicon tier: idle silicon routinely exceeds the + # ambient 104F threshold (subopi3 SoC idles at ~117F); 176F = 80C + # pre-throttle territory for Pi-Jetson SoCs and server CPUs [#733] - trigger: numeric_state entity_id: - - sensor.pfv_artroom_temperature - - sensor.pfv_garage_temperature - - sensor.pfv_tsys1_rack_temperature - sensor.pfv_tsys3_cpu_temperature - - sensor.pfv_tsys4_ambient_temperature - - sensor.pfv_tsys5_ambient_temperature - sensor.pfv_tsys6_cpu_temperature - sensor.pfv_tsys7_cpu_temperature - sensor.pfv_tsys9_cpu_temperature + - sensor.pfv_tsys7_drac_cpu1 + - sensor.pfv_tsys7_drac_cpu2 - sensor.pfv_jetson_temperature - sensor.pfv_svrpi_temperature - sensor.pfv_subopi3_temperature - sensor.pfv_subopi_dev_3_temperature - sensor.pfv_subopi_dev_4_temperature + above: 176 + - trigger: numeric_state + entity_id: + - sensor.pfv_artroom_temperature + - sensor.pfv_garage_temperature + - sensor.pfv_tsys1_rack_temperature + - sensor.pfv_tsys4_ambient_temperature + - sensor.pfv_tsys5_ambient_temperature - sensor.pfv_tsys6_drac_ambient - sensor.pfv_tsys7_drac_inlet - sensor.pfv_tsys7_drac_exhaust - - sensor.pfv_tsys7_drac_cpu1 - - sensor.pfv_tsys7_drac_cpu2 above: 104 actions: - action: notify.send_message