Files
PFVCluster/powerman
mrcharles a5eabf7692 feat(powerman): manage Cyclades PM10i PDU via powerman on pfv-tsys1
Set up centralized PDU management for a Cyclades AlterPath PM10i (10
controllable AC outlets) connected to pfv-tsys1 via a Prolific USB-to-DB9
serial adapter. powermand is now listening on 0.0.0.0:10101, making the
PDU manageable over the network from any host on the tailnet.

Scripts (powerman/):
- discover.sh: gather USB adapter, powerman state, device definitions
- setup.sh: idempotent setup — udev rule (stable symlink by serial number),
  powerman.conf with 10 outlet nodes, fix powermand dialout group, restart
  service. Overridable via env vars for other hosts/PDU types
- test-pdu.sh: validate control by cycling outlet 10 off then on (8/8 pass)
- status.sh: quick PDU status check

Issues fixed during setup:
- Config pointed at /dev/ttyUSB0 but adapter is at /dev/ttyUSB1 (fixed
  with udev symlink /dev/cyclades-pm10 pinned to adapter serial)
- powermand (user:powerman) lacked dialout group membership to open the
  serial device (fixed with usermod + udev GROUP="dialout")

Validation: outlet 10 turned off (confirmed), turned on (confirmed), then
cycled. All 10 outlets currently ON and manageable.

TODO tracked for Friday: rename outlets from generic (outlet-1..10) to
match physical devices, and change PDU admin password from factory default.

💘 Generated with Crush

Assisted-by: Crush:glm-5.2
2026-07-28 18:22:47 -05:00
..

Powerman PDU Management

Centralized power management for the Cyclades AlterPath PM10i PDU via Powerman, running on pfv-tsys1.

Hardware

Component Details
PDU Cyclades AlterPath PM10i (10 controllable AC outlets)
Firmware v1.9.0 (Aug 4, 2006)
Connection USB-to-DB9 adapter (Prolific pl2303, serial BJAAb144J07)
Host pfv-tsys1 (OptiPlex 9020, Proxmox)
Serial 9600 baud, 8N1, raw mode
Credentials Factory defaults: admin / pm8 (in cyclades-pm10.dev)
Network access powermand listens on 0.0.0.0:10101

Device mapping

USB adapter (067b:23a3, serial BJAAb144J07)
  └─ pl2303 driver → /dev/ttyUSB1
       └─ udev symlink → /dev/cyclades-pm10 (stable across reboots)
            └─ powermand reads/writes serial → Cyclades PM10i
                 └─ 10 outlets (factory default names: 1-10)

The udev rule (/etc/udev/rules.d/99-cyclades-pdu.rules) pins the adapter by its USB serial number, so the symlink survives replugs and reboots.

Scripts

All scripts run on the target host (pfv-tsys1) via tests/remote.sh:

# Setup (idempotent — safe to re-run):
PROX_HOST=pfv-tsys1 bash tests/remote.sh prox-file powerman/setup.sh

# Validate PDU control (cycles outlet 10 off → on):
PROX_HOST=pfv-tsys1 bash tests/remote.sh prox-file powerman/test-pdu.sh

# Status check:
PROX_HOST=pfv-tsys1 bash tests/remote.sh prox-file powerman/status.sh

Customizing for other hosts/PDUs

The setup script accepts environment overrides:

PDU_SERIAL=XXXX PDU_VENDOR=067b PDU_OUTLETS=20 PDU_TYPE=pm20 \
  PROX_HOST=other-host bash tests/remote.sh prox-file powerman/setup.sh

Usage (daily operations)

From pfv-tsys1 (or any host with network access to port 10101):

# List all outlets
powerman -l

# Query status (all outlets)
powerman -q

# Turn outlet off
powerman -0 outlet-10

# Turn outlet on
powerman -1 outlet-10

# Cycle outlet (off → 4s delay → on)
powerman -c outlet-10

# Query a specific outlet
powerman -q outlet-10

Remote access from other hosts

powermand listens on 0.0.0.0:10101. From another tailnet host:

powerman --server-host pfv-tsys1 --server-port 10101 -q

Or set POWERMAN_SERVER=pfv-tsys1:10101 in the environment.

Configuration files on pfv-tsys1

File Purpose
/etc/udev/rules.d/99-cyclades-pdu.rules Stable symlink for USB-DB9 adapter
/etc/powerman/powerman.conf Device definition + 10 outlet nodes
/etc/powerman/cyclades-pm10.dev Cyclades PM10 protocol spec (shipped with powerman)

Validation results

2026-07-28: All 8 checks passed. Outlet 10 turned OFF (confirmed), turned ON (confirmed), then cycled.

TODO (Friday onsite)

  • Rename outlets in /etc/powerman/powerman.conf to match the physical devices plugged into each outlet (e.g., node "tsys4-psu" "cyclades-pm10" "3"). Currently all outlets are generically named outlet-1 through outlet-10.
  • Change PDU admin password from factory default (pm8) if security-sensitive. Update /etc/powerman/cyclades-pm10.dev login script to match.
  • Verify all 10 outlets individually once device mapping is known.