mrcharles 5456c783c6 feat(ups): NUT setup for APC Smart-UPS C 1500 on pfv-tsys1
Deploy Network UPS Tools to monitor the server-room UPS units and feed data to
Home Assistant for power-usage tracking.

APC Smart-UPS C 1500 is fully operational: battery charge, runtime, load,
voltage, and status all reporting via usbhid-ups + APC HID 0.100 subdriver.
upsd listens on Tailscale (100.121.189.98:3493) for HA polling; local upsmon
provides graceful hypervisor shutdown on battery-low.

Key deployment fix: the udev rule must cover SUBSYSTEM=="usb" (raw
/dev/bus/usb) in addition to hidraw, because usbhid-ups opens the raw USB
device file after dropping to the nut user via setuid(). Matching only hidraw
causes EACCES on driver start.

Tripp Lite UPS (09ae:3016) is blocked — driver matches TrippLite HID 0.85
subdriver but fails reading the 878-byte HID Report Descriptor (EAGAIN via USB
hub). Needs physical reseat to direct motherboard USB port. Driver masked to
prevent restart-loop spam.

Files: ups/discover.sh, ups/setup.sh (idempotent), ups/status.sh, ups/README.md