All knowledge docs (architecture, runbooks, references, audits, policies) have been migrated to community.turnsys.com as wiki topics in the VP TechOps category. Discourse is now the canonical source of truth for documentation; git edit history no longer serves as the doc changelog. 37 .md files converted to short pointers linking to their Discourse topics. AGENTS.md updated with new documentation workflow policy. Code (scripts, configs, playbooks) remains authoritative in git.
This commit is contained in:
+9
-112
@@ -1,113 +1,10 @@
|
||||
# Powerman PDU Management
|
||||
# dcinfra/powerman/README.md
|
||||
|
||||
> **Redmine:** [#359](https://projects.knownelement.com/issues/359) (deployment, closed) · [#374](https://projects.knownelement.com/issues/374) (outlet renaming, open)
|
||||
|
||||
Centralized power management for the Cyclades AlterPath PM10i PDU via
|
||||
[Powerman](https://github.com/chaos/powerman), running on pfv-tsys1.
|
||||
|
||||
## Hardware
|
||||
|
||||
| Component | Details |
|
||||
|-----------|---------|
|
||||
| **PDU** | Cyclades AlterPath PM10i (10 controllable AC outlets) |
|
||||
| **Firmware** | v1.9.0 (Aug 4, 2006) |
|
||||
| **Connection** | USB-to-DB9 adapter (Prolific pl2303, serial BJAAb144J07) |
|
||||
| **Host** | pfv-tsys1 (OptiPlex 9020, Proxmox) |
|
||||
| **Serial** | 9600 baud, 8N1, raw mode |
|
||||
| **Credentials** | Factory defaults: `admin` / `pm8` (in cyclades-pm10.dev) |
|
||||
| **Network access** | powermand listens on `127.0.0.1:10101` (local) + `100.121.189.98:10101` (Tailscale) |
|
||||
|
||||
## Device mapping
|
||||
|
||||
```
|
||||
USB adapter (067b:23a3, serial BJAAb144J07)
|
||||
└─ pl2303 driver → /dev/ttyUSB1
|
||||
└─ udev symlink → /dev/cyclades-pm10 (stable across reboots)
|
||||
└─ powermand reads/writes serial → Cyclades PM10i
|
||||
└─ 10 outlets (factory default names: 1-10)
|
||||
```
|
||||
|
||||
The udev rule (`/etc/udev/rules.d/99-cyclades-pdu.rules`) pins the adapter
|
||||
by its USB serial number, so the symlink survives replugs and reboots.
|
||||
|
||||
## Scripts
|
||||
|
||||
All scripts run on the target host (pfv-tsys1) via `tests/remote.sh`:
|
||||
|
||||
```bash
|
||||
# Setup (idempotent — safe to re-run):
|
||||
PROX_HOST=pfv-tsys1 bash tests/remote.sh prox-file powerman/setup.sh
|
||||
|
||||
# Validate PDU control (cycles outlet 10 off → on):
|
||||
PROX_HOST=pfv-tsys1 bash tests/remote.sh prox-file powerman/test-pdu.sh
|
||||
|
||||
# Status check:
|
||||
PROX_HOST=pfv-tsys1 bash tests/remote.sh prox-file powerman/status.sh
|
||||
```
|
||||
|
||||
### Customizing for other hosts/PDUs
|
||||
|
||||
The setup script accepts environment overrides:
|
||||
|
||||
```bash
|
||||
PDU_SERIAL=XXXX PDU_VENDOR=067b PDU_OUTLETS=20 PDU_TYPE=pm20 \
|
||||
PROX_HOST=other-host bash tests/remote.sh prox-file powerman/setup.sh
|
||||
```
|
||||
|
||||
## Usage (daily operations)
|
||||
|
||||
From pfv-tsys1 (or any host with network access to port 10101):
|
||||
|
||||
```bash
|
||||
# List all outlets
|
||||
powerman -l
|
||||
|
||||
# Query status (all outlets)
|
||||
powerman -q
|
||||
|
||||
# Turn outlet off
|
||||
powerman -0 outlet-10
|
||||
|
||||
# Turn outlet on
|
||||
powerman -1 outlet-10
|
||||
|
||||
# Cycle outlet (off → 4s delay → on)
|
||||
powerman -c outlet-10
|
||||
|
||||
# Query a specific outlet
|
||||
powerman -q outlet-10
|
||||
```
|
||||
|
||||
### Remote access from other hosts
|
||||
|
||||
powermand listens on `0.0.0.0:10101`. From another tailnet host:
|
||||
|
||||
```bash
|
||||
powerman --server-host pfv-tsys1 --server-port 10101 -q
|
||||
```
|
||||
|
||||
Or set `POWERMAN_SERVER=pfv-tsys1:10101` in the environment.
|
||||
|
||||
## Configuration files on pfv-tsys1
|
||||
|
||||
| File | Purpose |
|
||||
|------|---------|
|
||||
| `/etc/udev/rules.d/99-cyclades-pdu.rules` | Stable symlink for USB-DB9 adapter |
|
||||
| `/etc/powerman/powerman.conf` | Device definition + 10 outlet nodes |
|
||||
| `/etc/powerman/cyclades-pm10.dev` | Cyclades PM10 protocol spec (shipped with powerman) |
|
||||
|
||||
## Validation results
|
||||
|
||||
2026-07-28: All 8 checks passed.
|
||||
Outlet 10 turned OFF (confirmed), turned ON (confirmed), then cycled.
|
||||
|
||||
## TODO (Friday onsite)
|
||||
|
||||
- [ ] **Rename outlets** in `/etc/powerman/powerman.conf` to match the
|
||||
physical devices plugged into each outlet (e.g., `node "tsys4-psu"
|
||||
"cyclades-pm10" "3"`). Currently all outlets are generically named
|
||||
`outlet-1` through `outlet-10`.
|
||||
- [ ] **Change PDU admin password** from factory default (`pm8`) if
|
||||
security-sensitive. Update `/etc/powerman/cyclades-pm10.dev` login
|
||||
script to match.
|
||||
- [ ] **Verify all 10 outlets** individually once device mapping is known.
|
||||
> **Documentation moved to Discourse — the canonical source of truth.**
|
||||
>
|
||||
> **Cyclades PM10i PDU management via powerman**
|
||||
>
|
||||
> **Read it here:** https://community.turnsys.com/t/301
|
||||
>
|
||||
> *Migrated 2026-08-06. This file is kept as a pointer for git-browsing context.
|
||||
> Do not update content here — edit the Discourse wiki topic instead.*
|
||||
|
||||
Reference in New Issue
Block a user