- id: pfv_plant_ups_on_battery
alias: PFV plant - UPS on battery
triggers:
- trigger: state
entity_id:
- sensor.tsys1_ups_status
- sensor.tsys9_ups_status
conditions:
- condition: template
value_template: '{{ ''On Battery'' in states(trigger.entity_id) }}'
actions:
- action: notify.send_message
target:
entity_id:
- notify.ultix_sidecar_new
- notify.allthes_ipad
data:
title: POWER OUTAGE
message: '{{ state_attr(trigger.entity_id, ''friendly_name'') }} lost utility
power and is ON BATTERY at {{ states(''sensor.'' ~ trigger.entity_id.split(''.'')[1]
| replace(''_status'', ''_battery_charge'')) }}% charge.'
mode: single
- id: pfv_plant_ups_battery_low
alias: PFV plant - UPS battery low
triggers:
- trigger: numeric_state
entity_id:
- sensor.tsys1_ups_battery_charge
below: 40
conditions:
- condition: template
value_template: '{{ ''On Battery'' in states(trigger.entity_id | replace(''_battery_charge'',
''_status'')) }}'
actions:
- action: notify.send_message
target:
entity_id:
- notify.ultix_sidecar_new
- notify.allthes_ipad
data:
title: UPS BATTERY LOW
message: '{{ trigger.entity_id }} at {{ states(trigger.entity_id) }}% while
on battery. Start graceful shutdown of VMs before hypervisors (#455 ordering).'
data:
priority: 1
mode: single
- id: pfv_plant_ups_comm_lost
alias: PFV plant - UPS communication lost
triggers:
- trigger: state
entity_id:
- sensor.tsys1_ups_status
- sensor.tsys9_ups_status
to: unavailable
for: 00:05:00
actions:
- action: notify.send_message
target:
entity_id:
- notify.ultix_sidecar_new
- notify.allthes_ipad
data:
title: UPS COMMS LOST
message: '{{ trigger.entity_id }} unreachable for 5 minutes (nut-server or network
path down; tsys1 also hosts pfv-bms itself).'
data:
priority: 1
mode: single
- id: pfv_plant_ups_power_restored
alias: PFV plant - utility power restored
triggers:
- trigger: state
entity_id:
- sensor.tsys1_ups_status
- sensor.tsys9_ups_status
conditions:
- condition: template
value_template: "{{ trigger.from_state is not none and 'On Battery' in trigger.from_state.state\n
\ and 'On Battery' not in states(trigger.entity_id) }}"
actions:
- action: notify.send_message
target:
entity_id:
- notify.ultix_sidecar_new
- notify.allthes_ipad
data:
title: Power restored
message: '{{ state_attr(trigger.entity_id, ''friendly_name'') }} is back ONLINE.'
mode: single
- id: pfv_plant_high_temperature
alias: PFV plant - high temperature
triggers:
- trigger: numeric_state
entity_id:
- sensor.pfv_artroom_temperature
- sensor.pfv_garage_temperature
- sensor.pfv_tsys1_rack_temperature
- sensor.pfv_tsys3_cpu_temperature
- sensor.pfv_tsys4_ambient_temperature
- sensor.pfv_tsys5_ambient_temperature
- sensor.pfv_tsys6_cpu_temperature
- sensor.pfv_tsys7_cpu_temperature
- sensor.pfv_tsys9_cpu_temperature
- sensor.pfv_jetson_temperature
- sensor.pfv_svrpi_temperature
- sensor.pfv_subopi3_temperature
- sensor.pfv_subopi_dev_3_temperature
- sensor.pfv_subopi_dev_4_temperature
- sensor.pfv_tsys6_drac_ambient
- sensor.pfv_tsys7_drac_inlet
- sensor.pfv_tsys7_drac_exhaust
- sensor.pfv_tsys7_drac_cpu1
- sensor.pfv_tsys7_drac_cpu2
above: 104
actions:
- action: notify.send_message
target:
entity_id:
- notify.ultix_sidecar_new
- notify.allthes_ipad
data:
title: HIGH TEMPERATURE
message: '{{ trigger.entity_id }} is {{ states(trigger.entity_id) }}°F (threshold
104°F). Check cooling/airflow.'
data:
priority: 1
mode: single
- id: pfv_plant_sensor_watchdog
alias: PFV plant - sensor watchdog (unavailable sensors)
description: HA is the environmental brain (#344) — a silent sensor is an outage.
Re-alert suppressed by 4h cooldown via last_notified input_text if present.
triggers:
- trigger: time_pattern
minutes: /30
actions:
- action: notify.send_message
target:
entity_id:
- notify.ultix_sidecar_new
- notify.allthes_ipad
data:
title: SENSOR WATCHDOG
message: >-
{% set fleet = states.sensor | selectattr('entity_id', 'match', 'sensor\.pfv_')
| list %}
{% set dead = fleet | selectattr('state', 'in', ['unavailable', 'unknown']) | list %}
{% if dead | length > 0 %}
{{ dead | length }} of {{ fleet | length }} fleet sensors silent:
{{ dead | map(attribute='entity_id') | join(', ') }}
{% else %}
all {{ fleet | length }} fleet sensors OK
{% endif %}
mode: single
- id: pfv_plant_temp_rising_fast
alias: PFV plant - temperature rising fast (rate-of-change)
description: Catches dead AC minutes before the 104F threshold trips.
triggers:
- trigger: state
entity_id:
- binary_sensor.server_room_temp_rising
- binary_sensor.tsys6_ambient_rising
- binary_sensor.tsys7_inlet_rising
- binary_sensor.garage_temp_rising
to: "on"
for:
minutes: 2
actions:
- action: notify.send_message
target:
entity_id:
- notify.ultix_sidecar_new
- notify.allthes_ipad
data:
title: TEMP RISING FAST
message: '{{ trigger.entity_id }} climbing ~10F/15min — check cooling
before the 104F threshold. (rate-of-change early warning)'
mode: single