Release: alert hygiene batch + UPS shutdown chain (dry-run) + restore runbook #3
@@ -0,0 +1,18 @@
|
||||
# STATUS — point-in-time agent state (sparse; history lives in Redmine)
|
||||
|
||||
Updated: 2026-09-06 ~07:10 CDT · dev @ aa8d788 · release @ 83b32d5
|
||||
|
||||
| ticket | tier | state | item |
|
||||
|---|---|---|---|
|
||||
| #811 | — | ⛔ | NeedsInput: merge PR #3, PVE tokens (#790), beta onboarding click, rotations |
|
||||
| #344 | prod | 🔄 | release PR #3 open, CI green, review gate passed (FAIL→fixed→dispositioned) |
|
||||
| #790 | dev | ✅ | shutdown chain DRY RUN, level-based re-polls; exec wiring waits on PVE tokens |
|
||||
| #628 | docs | ✅ | restore runbook + baseline backup 34a05d70 off-box on ultix |
|
||||
| #781 | beta | 🔄 | VM 53110 @ 192.168.3.240, HA up, owner created; onboarding form + config sync left |
|
||||
| #813 | — | ⏳ | CI check_config job parked — needs UI job log, recipe in ticket |
|
||||
| #345 | prod | 🔄 | rest_command verified registered; swap-back = founder re-test call |
|
||||
|
||||
## Inbox
|
||||
- 2026-09-06: tsys6 trend false-positive fix — watch trend sensors 24h post-deploy
|
||||
- 2026-09-06: stlpc-artroom dead all morning — policy ask in #811 item 8
|
||||
- 2026-09-06: runner container got external SIGTERM 11:35 UTC, restarted 11:37 — OAM check
|
||||
+60
-15
@@ -68,15 +68,36 @@
|
||||
mode: single
|
||||
- id: pfv_plant_ups_runtime_low
|
||||
alias: PFV plant - UPS runtime low while on battery
|
||||
description: On battery and runtime burned below 10 min — the graceful
|
||||
shutdown window is closing. VMs before hypervisors per #455.
|
||||
description: >-
|
||||
On battery and runtime burned below 10 min — the graceful shutdown
|
||||
window is closing. VMs before hypervisors per #455 ordering. Covers
|
||||
BOTH UPSes (APC + Tripp Lite — the Tripp Lite gap closed 2026-09-06);
|
||||
the status check maps each runtime sensor to its own UPS status.
|
||||
triggers:
|
||||
- trigger: numeric_state
|
||||
entity_id: sensor.pfv_ups_runtime_minutes
|
||||
entity_id:
|
||||
- sensor.pfv_ups_runtime_minutes
|
||||
- sensor.pfv_tripp_lite_runtime_minutes
|
||||
below: 10
|
||||
# 5-min level re-check: numeric_state alone fires only on the threshold
|
||||
# CROSSING — a blip at that minute (or an HA restart mid-outage) would
|
||||
# silence the page for the whole discharge. Level-based polling turns
|
||||
# this into an escalation ladder while the outage persists.
|
||||
- trigger: time_pattern
|
||||
minutes: /5
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: "{{ states('sensor.tsys1_ups_status') not in ['Online', 'unknown', 'unavailable'] }}"
|
||||
value_template: >-
|
||||
{% set ns = namespace(hit=false) %}
|
||||
{% for rt, st in [
|
||||
('sensor.pfv_ups_runtime_minutes', 'sensor.tsys1_ups_status'),
|
||||
('sensor.pfv_tripp_lite_runtime_minutes', 'sensor.tsys1_triplite_status')] %}
|
||||
{% if is_number(states(rt)) and (states(rt) | float) < 10
|
||||
and states(st) not in ['Online', 'OL', 'unknown', 'unavailable'] %}
|
||||
{% set ns.hit = true %}
|
||||
{% endif %}
|
||||
{% endfor %}
|
||||
{{ ns.hit }}
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
@@ -86,7 +107,7 @@
|
||||
data:
|
||||
title: UPS RUNTIME LOW
|
||||
url: /lovelace-pfv-server-room/ups
|
||||
message: On battery {{ states('sensor.pfv_ups_runtime_minutes') }} min left — start graceful shutdown now (#455 ordering).
|
||||
message: '{{ state_attr(trigger.entity_id, ''friendly_name'') }}: {{ states(trigger.entity_id) }} min left — start graceful shutdown now (#455 ordering).'
|
||||
mode: single
|
||||
- id: pfv_plant_ups_power_restored
|
||||
alias: PFV plant - utility power restored
|
||||
@@ -190,12 +211,32 @@
|
||||
mode: single
|
||||
- id: pfv_plant_sensor_watchdog
|
||||
alias: PFV plant - sensor watchdog (unavailable sensors)
|
||||
description: HA is the environmental brain (#344) — a silent sensor is an outage.
|
||||
Re-alert suppressed by 4h cooldown via last_notified input_text if present.
|
||||
description: >
|
||||
HA is the environmental brain (#344) — a silent sensor is an outage.
|
||||
Fleet-wide sweep (every pfv_* sensor, broader than the 5-min critical
|
||||
watchdog). PUSHES ONLY when sensors are actually dead, and re-pages a
|
||||
still-dead fleet at most every 4h — the unconditional 30-min page was
|
||||
retired 2026-09-06 after live-fire alert fatigue. All-OK cycles log
|
||||
quietly; the Kuma dead-man heartbeat (#792) owns liveness signaling.
|
||||
mode: single
|
||||
max_exceeded: silent
|
||||
triggers:
|
||||
- trigger: time_pattern
|
||||
minutes: /30
|
||||
actions:
|
||||
- variables:
|
||||
fleet: "{{ states.sensor | selectattr('entity_id', 'match', 'sensor\\.pfv_') | list }}"
|
||||
dead: "{{ fleet | selectattr('state', 'in', ['unavailable', 'unknown']) | list }}"
|
||||
# 4h cooldown: page again only if the last page is older than 4h
|
||||
# (or we never paged). Fresh HA start (no restore) counts as never.
|
||||
# as_timestamp math — aware/naive datetime subtraction throws in Jinja.
|
||||
notify_gate: >-
|
||||
{{ states('input_datetime.pfv_plant_watchdog_last_notify') in ['unknown', 'unavailable', 'none']
|
||||
or as_timestamp(now()) - as_timestamp(states('input_datetime.pfv_plant_watchdog_last_notify')) > 14400 }}
|
||||
- if:
|
||||
- condition: template
|
||||
value_template: "{{ dead | length > 0 and notify_gate }}"
|
||||
then:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id:
|
||||
@@ -205,16 +246,20 @@
|
||||
title: SENSOR WATCHDOG
|
||||
url: /lovelace-pfv-server-room/overview
|
||||
message: >-
|
||||
{% set fleet = states.sensor | selectattr('entity_id', 'match', 'sensor\.pfv_')
|
||||
| list %}
|
||||
{% set dead = fleet | selectattr('state', 'in', ['unavailable', 'unknown']) | list %}
|
||||
{% if dead | length > 0 %}
|
||||
{{ dead | length }} of {{ fleet | length }} fleet sensors silent:
|
||||
{{ dead | map(attribute='entity_id') | join(', ') }}
|
||||
{% else %}
|
||||
all {{ fleet | length }} fleet sensors OK
|
||||
{% endif %}
|
||||
mode: single
|
||||
- action: input_datetime.set_datetime
|
||||
target:
|
||||
entity_id: input_datetime.pfv_plant_watchdog_last_notify
|
||||
data:
|
||||
datetime: "{{ now().strftime('%Y-%m-%d %H:%M:%S') }}"
|
||||
else:
|
||||
- action: logbook.log
|
||||
data:
|
||||
name: Plant watchdog
|
||||
message: >-
|
||||
Sweep: all {{ fleet | length }} fleet sensors answering
|
||||
({{ dead | length }} silent, cooldown {{ 'active' if not notify_gate else 'n/a' }}).
|
||||
- id: pfv_plant_temp_rising_fast
|
||||
alias: PFV plant - temperature rising fast (rate-of-change)
|
||||
description: Catches dead AC minutes before the 104F threshold trips.
|
||||
|
||||
@@ -56,3 +56,12 @@ input_boolean:
|
||||
pfv_watchdog_auto_restart:
|
||||
name: Watchdog auto core restart
|
||||
icon: mdi:restart-alert
|
||||
|
||||
# 30-min plant watchdog cooldown (#344, 2026-09-06): re-pages a dead sensor
|
||||
# at most every 4h instead of every cycle. Set by the automation on notify.
|
||||
input_datetime:
|
||||
pfv_plant_watchdog_last_notify:
|
||||
name: Plant watchdog last notify
|
||||
has_date: true
|
||||
has_time: true
|
||||
icon: mdi:bell-cancel
|
||||
|
||||
@@ -0,0 +1,78 @@
|
||||
# pfv-bms restore runbook (#628)
|
||||
|
||||
Three restore layers exist. Work **inside-out**: usually only layer 1 is
|
||||
needed. Restore drills run on the **dev lane only** — never on hosts
|
||||
running prod VMs (standing rule after the 2026-09-03 PBS drill that
|
||||
I/O-starved prod HA, #684 / t/298).
|
||||
|
||||
## Layer 0 — what is NOT in git
|
||||
|
||||
| Artifact | Where it lives | Covered by |
|
||||
|----------|----------------|------------|
|
||||
| `secrets.yaml` (tokens, webhook ids, unlock URL) | on-box `/config/secrets.yaml` | Layer 1 + 2 backups |
|
||||
| `.storage/` (dashboards-in-storage, registry, auth) | on-box `/config/.storage/` | Layer 1 + 2 backups |
|
||||
| Zigbee/HomeKit/BT pairings | on-box | Layer 1 + 2 backups |
|
||||
|
||||
Git (this repo, `release` branch) is the source of truth for
|
||||
configuration **YAML only**. A fresh box restored from git still needs a
|
||||
`secrets.yaml` re-provisioned from the keeper's records (~/.creds notes
|
||||
+ badge/webhook ids) before HA will start.
|
||||
|
||||
## Layer 1 — HA-level backup (config + settings, small, fast)
|
||||
|
||||
Taken on-box via the `ha` CLI; produces a self-contained `.tar`:
|
||||
|
||||
```bash
|
||||
ssh -p 22222 root@pfv-bms.knel.net 'ha backups new --name "pfv-bms-$(date +%F)"'
|
||||
ssh -p 22222 root@pfv-bms.knel.net 'ha backups list' # find slug
|
||||
ssh -p 22222 root@pfv-bms.knel.net 'ha backups info <slug>' # verify size/state
|
||||
# OFF-BOX COPY (the on-box copy dies with the VM disk):
|
||||
scp -P 22222 'root@pfv-bms.knel.net:/mnt/data/supervisor/backup/<slug>.tar' /backup/destination/
|
||||
```
|
||||
|
||||
HAOS automatic backups are CONFIRMED LIVE (daily "Automatic backup"
|
||||
entries observed 2026-09-05/06) — layer 1 has a baseline; the off-box
|
||||
copy remains the manual step.
|
||||
|
||||
Restore (same or fresh HAOS box):
|
||||
|
||||
```bash
|
||||
scp -P 22222 backup.tar root@pfv-bms.knel.net:/mnt/data/supervisor/backup/
|
||||
ssh -p 22222 root@pfv-bms.knel.net 'ha backups restore <slug> --type full'
|
||||
```
|
||||
|
||||
Baseline on record: slug `34a05d70`, name
|
||||
`pfv-bms-baseline-2026-09-06-post-790`, 788 MB compressed, taken after
|
||||
the alert-hygiene + #790 batches (dev `c4ebb8a`). Off-box copy:
|
||||
`~/projects/KNEL/PhysicalPlant/pfv-bms-backups/` on ultix-streaming
|
||||
(sha256 6ff2fa6bd5f3dd2f2a47…).
|
||||
|
||||
## Layer 2 — VM-level backup (prod PBS, nightly)
|
||||
|
||||
- All prod VMs — **including VM 100 (pfv-bms) on pfv-tsys1** — back up
|
||||
nightly to prod PBS, staggered 21:00–04:30 Central, throttled
|
||||
60/30 MiB/s + job bwlimit 50 MiB/s (founder ruling t/321).
|
||||
- Restore: PVE web UI or `qmrestore` — **target a scratch VM on the dev
|
||||
lane** (verify the restore boots there), never restore in place over
|
||||
the live VM without a Kuma maintenance window.
|
||||
- Gap (open, OAM lane): pfv-tsys5 has no PBS job yet — beta/test VMs on
|
||||
tsys5 are unprotected; fine for beta, not for anything promoted.
|
||||
|
||||
## Layer 3 — config-from-git (last resort, fresh HAOS)
|
||||
|
||||
1. Flash/install HAOS, complete onboarding, join Tailscale.
|
||||
2. `git clone git.knownelement.com:KNEL/KNELBMS` → copy tree to `/config`
|
||||
at the `release` HEAD the fleet expects.
|
||||
3. Re-provision `secrets.yaml` (Layer 0 table) — from keeper records.
|
||||
4. `ha core check` before starting; then watch the first boot: the
|
||||
post-deploy validation automation pages if criticals fail to
|
||||
materialize (#778).
|
||||
5. Verify the trail: deploy sensor matches `release` HEAD, Kuma
|
||||
heartbeat green, doorman roster sensors populated.
|
||||
|
||||
## Related
|
||||
|
||||
- Deploy pipeline + gate: README "Deployment pipeline"; `ha core check`
|
||||
on-box before any release push.
|
||||
- Incident history: #684 (PBS drill), #780 (tsys1 storage), t/298
|
||||
(Sep 3 wedge), t/320 (reload vs restart deploy semantics).
|
||||
@@ -84,11 +84,14 @@ input_boolean:
|
||||
|
||||
shell_command:
|
||||
# Unlock dispatch via curl — swapped from rest_command 2026-09-04: the
|
||||
# rest_command integration silently fails to register on this box
|
||||
# (404 on /api/services/rest_command despite valid config + secret;
|
||||
# root-cause pending in #345/#741). curl is present in the HA core
|
||||
# container. Token lives in the URL secret — process-list exposure
|
||||
# accepted (isolated container).
|
||||
# rest_command integration silently failed to register on this box
|
||||
# (404 on /api/services/rest_command despite valid config + secret).
|
||||
# NOT reproducible: 2026-09-06 the integration + doorman_unlock service
|
||||
# are registered again (suspect: transient state after a reload-only
|
||||
# deploy window; rest_command now also exposes a reload service).
|
||||
# curl stays as the verified-live dispatch path — swapping back to
|
||||
# rest_command (drops the token from the process list) is gated on one
|
||||
# armed badge re-test (founder call, questions-v1).
|
||||
doorman_unlock: "curl -sS -m 10 '{{ doorman_unlock_url }}'"
|
||||
|
||||
rest_command:
|
||||
|
||||
@@ -543,26 +543,56 @@ sensor:
|
||||
unique_id: pfv_garage_pdu_energy
|
||||
|
||||
# --- Rate-of-change early warning (#682): +10°F/15min = AC trouble [#344] ---
|
||||
# DRAC sensors quantize to whole °C and FLAP ~1.8°F between polls; raw-fed
|
||||
# trend sensors false-tripped TEMP RISING FAST (2026-09-06 05:02 CDT, tsys6).
|
||||
# Trend inputs are 5-min time-weighted moving averages — real climbs survive
|
||||
# the smoothing, quantization flapping does not.
|
||||
filter:
|
||||
- platform: time_simple_moving_average
|
||||
name: "PFV tsys1 rack temperature smoothed"
|
||||
entity_id: sensor.pfv_tsys1_rack_temperature
|
||||
window: "00:05:00"
|
||||
precision: 2
|
||||
unique_id: pfv_tsys1_rack_temperature_smoothed
|
||||
- platform: time_simple_moving_average
|
||||
name: "PFV tsys6 DRAC ambient smoothed"
|
||||
entity_id: sensor.pfv_tsys6_drac_ambient
|
||||
window: "00:05:00"
|
||||
precision: 2
|
||||
unique_id: pfv_tsys6_drac_ambient_smoothed
|
||||
- platform: time_simple_moving_average
|
||||
name: "PFV tsys7 DRAC inlet smoothed"
|
||||
entity_id: sensor.pfv_tsys7_drac_inlet
|
||||
window: "00:05:00"
|
||||
precision: 2
|
||||
unique_id: pfv_tsys7_drac_inlet_smoothed
|
||||
- platform: time_simple_moving_average
|
||||
name: "PFV garage temperature smoothed"
|
||||
entity_id: sensor.pfv_garage_temperature
|
||||
window: "00:05:00"
|
||||
precision: 2
|
||||
unique_id: pfv_garage_temperature_smoothed
|
||||
|
||||
binary_sensor:
|
||||
- platform: trend
|
||||
sensors:
|
||||
server_room_temp_rising:
|
||||
entity_id: sensor.pfv_tsys1_rack_temperature
|
||||
entity_id: sensor.pfv_tsys1_rack_temperature_smoothed
|
||||
sample_duration: 900
|
||||
min_gradient: 0.011
|
||||
unique_id: trend_server_room_rising
|
||||
tsys6_ambient_rising:
|
||||
entity_id: sensor.pfv_tsys6_drac_ambient
|
||||
entity_id: sensor.pfv_tsys6_drac_ambient_smoothed
|
||||
sample_duration: 900
|
||||
min_gradient: 0.011
|
||||
unique_id: trend_tsys6_ambient_rising
|
||||
tsys7_inlet_rising:
|
||||
entity_id: sensor.pfv_tsys7_drac_inlet
|
||||
entity_id: sensor.pfv_tsys7_drac_inlet_smoothed
|
||||
sample_duration: 900
|
||||
min_gradient: 0.011
|
||||
unique_id: trend_tsys7_inlet_rising
|
||||
garage_temp_rising:
|
||||
entity_id: sensor.pfv_garage_temperature
|
||||
entity_id: sensor.pfv_garage_temperature_smoothed
|
||||
sample_duration: 900
|
||||
min_gradient: 0.011
|
||||
unique_id: trend_garage_rising
|
||||
|
||||
@@ -0,0 +1,149 @@
|
||||
# ============================================================================
|
||||
# UPS graceful-shutdown chain (#790) — the #455 ordering, automated
|
||||
# ============================================================================
|
||||
# DESIGN (unchanged from the 2026-09-05 session spec):
|
||||
# DRY_RUN is the DEFAULT and the shipped mode. The chain LOGS + PAGES the
|
||||
# exact shutdown plan (#455: VMs before hypervisors, pfv-bms last of the
|
||||
# VMs — the brain stays alive as long as possible). Execution (real
|
||||
# qmshutdown / PVE API calls) is double-gated:
|
||||
# 1. input_boolean.pfv_ups_shutdown_armed — founder arm, default OFF
|
||||
# 2. input_boolean.pfv_ups_shutdown_dry_run — default ON
|
||||
# Arming for the Sept 11-12 live test needs, in order: founder review of
|
||||
# the VM ordering below (edit this file via PR), PVE API tokens provisioned
|
||||
# into on-box secrets.yaml (NeedsInput ticket), then a supervised live test.
|
||||
#
|
||||
# PLAN DATA — captured from LIVE inventory 2026-09-06 (qm list, all hosts):
|
||||
# tsys1: 100 pfv-bms, 101 tsys-ca, 102 k8s-cnode1, 103 netinfra-01,
|
||||
# 104 librenms, 105 pve-datacenter | tsys3: 313 k8s-wnode
|
||||
# tsys4: 400 PBS | tsys5: test/preprod bed (5xxx) | tsys6: 600-605
|
||||
# tsys7: 701-711, 902 | tsys9: 904, 905
|
||||
# ============================================================================
|
||||
|
||||
input_boolean:
|
||||
# NOTE: `initial:` wins over restored state at EVERY HA start — a deploy
|
||||
# mid-test silently reverts these to the safe defaults (armed OFF,
|
||||
# dry-run ON). Safe direction, but re-arm after any restart during the
|
||||
# supervised Sept 11-12 live test.
|
||||
pfv_ups_shutdown_armed:
|
||||
name: UPS shutdown chain ARMED
|
||||
description: Founder-level arm. ON + dry-run OFF = real shutdown dispatch.
|
||||
icon: mdi:power-standby
|
||||
initial: false
|
||||
pfv_ups_shutdown_dry_run:
|
||||
name: UPS shutdown DRY RUN
|
||||
description: ON (default) = log/page the plan only, touch nothing.
|
||||
icon: mdi:numeric-1-box-outline
|
||||
initial: true
|
||||
|
||||
input_datetime:
|
||||
pfv_ups_shutdown_last_page:
|
||||
name: UPS shutdown last plan page
|
||||
has_date: true
|
||||
has_time: true
|
||||
icon: mdi:clock-alert-outline
|
||||
|
||||
automation:
|
||||
- id: pfv_ups_shutdown_plan
|
||||
alias: PFV UPS shutdown - plan (dry-run by default)
|
||||
description: >-
|
||||
On battery with the shutdown window opening (runtime < 20 min or
|
||||
charge < 50%), log + page the #455 ordered plan. Re-pages at most
|
||||
every 6h per outage. When armed AND dry-run OFF (founder + supervised
|
||||
test only), the plan page says EXECUTE — real dispatch wiring lands
|
||||
with PVE API tokens (#790 NeedsInput); until then nothing but text
|
||||
can be emitted by this automation.
|
||||
mode: single
|
||||
max_exceeded: silent
|
||||
triggers:
|
||||
- trigger: numeric_state
|
||||
entity_id:
|
||||
- sensor.pfv_ups_runtime_minutes
|
||||
- sensor.pfv_tripp_lite_runtime_minutes
|
||||
below: 20
|
||||
- trigger: numeric_state
|
||||
entity_id:
|
||||
- sensor.tsys1_ups_battery_charge
|
||||
- sensor.tsys1_triplite_battery_charge
|
||||
below: 50
|
||||
# 5-min level re-check — same edge-vs-level reasoning as the
|
||||
# runtime-low alert: never let a threshold-crossing blip silence
|
||||
# the plan page for an entire discharge.
|
||||
- trigger: time_pattern
|
||||
minutes: /5
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{% set ns = namespace(hit=false) %}
|
||||
{% for rt, st in [
|
||||
('sensor.pfv_ups_runtime_minutes', 'sensor.tsys1_ups_status'),
|
||||
('sensor.pfv_tripp_lite_runtime_minutes', 'sensor.tsys1_triplite_status')] %}
|
||||
{% if is_number(states(rt)) and (states(rt) | float) < 20
|
||||
and states(st) not in ['Online', 'OL', 'unknown', 'unavailable'] %}
|
||||
{% set ns.hit = true %}
|
||||
{% endif %}
|
||||
{% endfor %}
|
||||
{% for ch, st in [
|
||||
('sensor.tsys1_ups_battery_charge', 'sensor.tsys1_ups_status'),
|
||||
('sensor.tsys1_triplite_battery_charge', 'sensor.tsys1_triplite_status')] %}
|
||||
{% if is_number(states(ch)) and (states(ch) | float) < 50
|
||||
and states(st) not in ['Online', 'OL', 'unknown', 'unavailable'] %}
|
||||
{% set ns.hit = true %}
|
||||
{% endif %}
|
||||
{% endfor %}
|
||||
{{ ns.hit }}
|
||||
# Status 'unavailable' suppresses (anti-noise); UPS COMMS LOST covers
|
||||
# that failure mode separately after 5 min.
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{{ states('input_datetime.pfv_ups_shutdown_last_page') in ['unknown', 'unavailable', 'none']
|
||||
or as_timestamp(now()) - as_timestamp(states('input_datetime.pfv_ups_shutdown_last_page')) > 21600 }}
|
||||
actions:
|
||||
- variables:
|
||||
execute_mode: >-
|
||||
{{ is_state('input_boolean.pfv_ups_shutdown_armed', 'on')
|
||||
and not is_state('input_boolean.pfv_ups_shutdown_dry_run', 'on') }}
|
||||
plan: >-
|
||||
UPS ON BATTERY — #455 shutdown plan (VMs before hypervisors):
|
||||
1. tsys5 test bed: qmshutdown 5105 awx, 5101 siem, 51017 sec onion,
|
||||
53100-53102 preprod, 5108-5109, 513 sectestbed k8s, 5000 sandbox
|
||||
2. k8s workers: tsys9 905, tsys7 701, tsys6 601, tsys3 313
|
||||
(drain + shutdown; cnodes 102/603/705 after workers)
|
||||
3. LOB/infra VMs: tsys6 600 awx, 602/605, tsys7 702 uisp, 703, 706-711,
|
||||
902 ucs-2, 604/711 mailgw (after queue drain), tsys9 904 netinfra-02
|
||||
4. tsys1: 104 librenms, 105 pve-dc, 103 netinfra-01, 101 tsys-ca
|
||||
(ca LAST — signing path for everything above)
|
||||
5. pfv-bms VM 100 LAST of the VMs — the brain stays up until now
|
||||
6. Hypervisors: iDRAC graceful off tsys6/tsys7 (PowerEdge);
|
||||
tsys1, tsys3, tsys4, tsys5, tsys9 idle out on UPS exhaustion
|
||||
(OptiPlex/Precision, no BMC)
|
||||
mode_note: >-
|
||||
{{ 'MODE: EXECUTE (armed, live dispatch)' if execute_mode
|
||||
else 'MODE: DRY RUN (plan only — nothing will be shut down)' }}
|
||||
- action: logbook.log
|
||||
data:
|
||||
name: UPS shutdown chain
|
||||
message: "{{ mode_note }} Plan: {{ plan | truncate(250) }}"
|
||||
- action: notify.send_message
|
||||
target:
|
||||
entity_id:
|
||||
- notify.ultix_sidecar_new
|
||||
- notify.allthes_ipad
|
||||
data:
|
||||
title: "{{ 'UPS SHUTDOWN EXECUTING' if execute_mode else 'UPS SHUTDOWN PLAN (dry run)' }}"
|
||||
url: /lovelace-pfv-server-room/ups
|
||||
message: >-
|
||||
{{ mode_note }} Runtime APC {{ states('sensor.pfv_ups_runtime_minutes') }}
|
||||
min / TrippLite {{ states('sensor.pfv_tripp_lite_runtime_minutes') }} min.
|
||||
Order: test bed → k8s workers → LOB VMs → tsys1 infra → CA →
|
||||
pfv-bms (100) last → hypervisors. Full plan in the logbook.
|
||||
- action: persistent_notification.create
|
||||
data:
|
||||
title: "{{ 'UPS SHUTDOWN EXECUTING' if execute_mode else 'UPS SHUTDOWN PLAN (dry run)' }}"
|
||||
message: "{{ plan }}"
|
||||
# Suppression stamp set LAST — a failed notify must not suppress the
|
||||
# next 5-min re-page cycle.
|
||||
- action: input_datetime.set_datetime
|
||||
target:
|
||||
entity_id: input_datetime.pfv_ups_shutdown_last_page
|
||||
data:
|
||||
datetime: "{{ now().strftime('%Y-%m-%d %H:%M:%S') }}"
|
||||
Vendored
+7
@@ -0,0 +1,7 @@
|
||||
# CI-only stub for `homeassistant check_config` (see .gitea/workflows/ci.yml).
|
||||
# NEVER copied to the live box. Values are syntactically-valid placeholders.
|
||||
deploy_webhook_id: ci-stub-deploy-webhook
|
||||
doorman_scan_webhook_id: ci-stub-scan-webhook
|
||||
doorman_unlock_url: http://127.0.0.1:1/unlock-stub
|
||||
gitea_auth_header: token ci-stub-gitea-token
|
||||
kuma_push_url: http://127.0.0.1:1/push?status=up&msg=ci-stub
|
||||
@@ -47,5 +47,46 @@ echo "=== secrets ==="
|
||||
t "no private keys in tree" \
|
||||
"! grep -rInE 'BEGIN (RSA |OPENSSH |EC |DSA )?PRIVATE KEY' --exclude-dir=.git --exclude-dir=docs ."
|
||||
|
||||
echo "=== alert hygiene: push only when something is wrong (2026-09-06 live-fire) ==="
|
||||
# The 30-min sweep used to page every cycle even when the fleet was all-OK
|
||||
# (48 pages/day of noise). Notify must sit behind the dead>0 + 4h-cooldown gate.
|
||||
t "plant watchdog notify gated (dead-only + cooldown input)" \
|
||||
"grep -q 'pfv_plant_watchdog_last_notify' configuration.yaml && grep -q 'notify_gate' automations.yaml"
|
||||
|
||||
# tsys6 DRAC ambient quantizes to whole degrees C and flaps ~2F; the raw-fed
|
||||
# trend sensor tripped TEMP RISING FAST with zero real climb (2026-09-06 05:02 CDT).
|
||||
t "trend sensors fed from smoothed sources" \
|
||||
"grep -q 'time_simple_moving_average' packages/plant_snmp.yaml && sed -n '/^binary_sensor:/,/^utility_meter:/p' packages/plant_snmp.yaml | grep -q 'entity_id: sensor.pfv_tsys6_drac_ambient_smoothed'"
|
||||
|
||||
# Tripp Lite had runtime sensors but no runtime-low alert — half the plant's
|
||||
# shutdown window was unmonitored.
|
||||
t "runtime-low covers Tripp Lite" \
|
||||
"sed -n '/id: pfv_plant_ups_runtime_low/,/^ mode:/p' automations.yaml | grep -q 'sensor.pfv_tripp_lite_runtime_minutes'"
|
||||
t "runtime-low status check maps per-UPS" \
|
||||
"sed -n '/id: pfv_plant_ups_runtime_low/,/^ mode:/p' automations.yaml | grep -q \"sensor.pfv_tripp_lite_runtime_minutes', 'sensor.tsys1_triplite_status'\""
|
||||
|
||||
echo "=== UPS shutdown chain (#790 — dry-run is the shipped mode) ==="
|
||||
t "shutdown chain package present, dry-run default ON" \
|
||||
"grep -q 'id: pfv_ups_shutdown_plan' packages/ups_shutdown.yaml && grep -A4 'pfv_ups_shutdown_dry_run:' packages/ups_shutdown.yaml | grep -q 'initial: true'"
|
||||
t "armed switch default OFF" \
|
||||
"grep -A4 'pfv_ups_shutdown_armed:' packages/ups_shutdown.yaml | grep -q 'initial: false'"
|
||||
# Host coverage must hold in the PLAN BODY, not the header comment —
|
||||
# scope the grep to the plan template variable.
|
||||
PLAN_OK=1
|
||||
for h in tsys1 tsys3 tsys4 tsys5 tsys6 tsys7 tsys9; do
|
||||
# full-read grep (not -q): the script runs with pipefail — -q's early
|
||||
# exit SIGPIPEs sed and flips the pipeline status to 141
|
||||
sed -n '/plan: >-/,/mode_note:/p' packages/ups_shutdown.yaml | grep "$h" >/dev/null || PLAN_OK=0
|
||||
done
|
||||
t "plan covers all seven hypervisors (plan body)" "[ \$PLAN_OK -eq 1 ]"
|
||||
t "pfv-bms VM 100 ordered last of the VMs (#455)" \
|
||||
"grep -q 'pfv-bms VM 100 LAST' packages/ups_shutdown.yaml"
|
||||
|
||||
echo "=== level-based re-checks (review finding: edge-only triggers miss pages) ==="
|
||||
t "runtime-low re-polls every 5 min" \
|
||||
"sed -n '/id: pfv_plant_ups_runtime_low/,/^ mode:/p' automations.yaml | grep -q 'minutes: /5'"
|
||||
t "shutdown chain re-polls every 5 min" \
|
||||
"grep -A30 'id: pfv_ups_shutdown_plan' packages/ups_shutdown.yaml | grep -q 'minutes: /5'"
|
||||
|
||||
echo "=== SDLC SUITE: $FAIL failures ==="
|
||||
exit "$FAIL"
|
||||
|
||||
Reference in New Issue
Block a user