Release: alert hygiene batch + UPS shutdown chain (dry-run) + restore runbook #3
+16
-5
@@ -79,14 +79,25 @@
|
||||
- sensor.pfv_ups_runtime_minutes
|
||||
- sensor.pfv_tripp_lite_runtime_minutes
|
||||
below: 10
|
||||
# 5-min level re-check: numeric_state alone fires only on the threshold
|
||||
# CROSSING — a blip at that minute (or an HA restart mid-outage) would
|
||||
# silence the page for the whole discharge. Level-based polling turns
|
||||
# this into an escalation ladder while the outage persists.
|
||||
- trigger: time_pattern
|
||||
minutes: /5
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{% set status_map = {
|
||||
'sensor.pfv_ups_runtime_minutes': 'sensor.tsys1_ups_status',
|
||||
'sensor.pfv_tripp_lite_runtime_minutes': 'sensor.tsys1_triplite_status'} %}
|
||||
{{ states(status_map.get(trigger.entity_id, 'sensor.tsys1_ups_status'))
|
||||
not in ['Online', 'OL', 'unknown', 'unavailable'] }}
|
||||
{% set ns = namespace(hit=false) %}
|
||||
{% for rt, st in [
|
||||
('sensor.pfv_ups_runtime_minutes', 'sensor.tsys1_ups_status'),
|
||||
('sensor.pfv_tripp_lite_runtime_minutes', 'sensor.tsys1_triplite_status')] %}
|
||||
{% if is_number(states(rt)) and (states(rt) | float) < 10
|
||||
and states(st) not in ['Online', 'OL', 'unknown', 'unavailable'] %}
|
||||
{% set ns.hit = true %}
|
||||
{% endif %}
|
||||
{% endfor %}
|
||||
{{ ns.hit }}
|
||||
actions:
|
||||
- action: notify.send_message
|
||||
target:
|
||||
|
||||
+38
-13
@@ -20,6 +20,10 @@
|
||||
# ============================================================================
|
||||
|
||||
input_boolean:
|
||||
# NOTE: `initial:` wins over restored state at EVERY HA start — a deploy
|
||||
# mid-test silently reverts these to the safe defaults (armed OFF,
|
||||
# dry-run ON). Safe direction, but re-arm after any restart during the
|
||||
# supervised Sept 11-12 live test.
|
||||
pfv_ups_shutdown_armed:
|
||||
name: UPS shutdown chain ARMED
|
||||
description: Founder-level arm. ON + dry-run OFF = real shutdown dispatch.
|
||||
@@ -61,26 +65,39 @@ automation:
|
||||
- sensor.tsys1_ups_battery_charge
|
||||
- sensor.tsys1_triplite_battery_charge
|
||||
below: 50
|
||||
# 5-min level re-check — same edge-vs-level reasoning as the
|
||||
# runtime-low alert: never let a threshold-crossing blip silence
|
||||
# the plan page for an entire discharge.
|
||||
- trigger: time_pattern
|
||||
minutes: /5
|
||||
conditions:
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{% set sm = {
|
||||
'sensor.pfv_ups_runtime_minutes': 'sensor.tsys1_ups_status',
|
||||
'sensor.pfv_tripp_lite_runtime_minutes': 'sensor.tsys1_triplite_status',
|
||||
'sensor.tsys1_ups_battery_charge': 'sensor.tsys1_ups_status',
|
||||
'sensor.tsys1_triplite_battery_charge': 'sensor.tsys1_triplite_status'} %}
|
||||
{{ states(sm.get(trigger.entity_id, 'sensor.tsys1_ups_status'))
|
||||
not in ['Online', 'OL', 'unknown', 'unavailable'] }}
|
||||
{% set ns = namespace(hit=false) %}
|
||||
{% for rt, st in [
|
||||
('sensor.pfv_ups_runtime_minutes', 'sensor.tsys1_ups_status'),
|
||||
('sensor.pfv_tripp_lite_runtime_minutes', 'sensor.tsys1_triplite_status')] %}
|
||||
{% if is_number(states(rt)) and (states(rt) | float) < 20
|
||||
and states(st) not in ['Online', 'OL', 'unknown', 'unavailable'] %}
|
||||
{% set ns.hit = true %}
|
||||
{% endif %}
|
||||
{% endfor %}
|
||||
{% for ch, st in [
|
||||
('sensor.tsys1_ups_battery_charge', 'sensor.tsys1_ups_status'),
|
||||
('sensor.tsys1_triplite_battery_charge', 'sensor.tsys1_triplite_status')] %}
|
||||
{% if is_number(states(ch)) and (states(ch) | float) < 50
|
||||
and states(st) not in ['Online', 'OL', 'unknown', 'unavailable'] %}
|
||||
{% set ns.hit = true %}
|
||||
{% endif %}
|
||||
{% endfor %}
|
||||
{{ ns.hit }}
|
||||
# Status 'unavailable' suppresses (anti-noise); UPS COMMS LOST covers
|
||||
# that failure mode separately after 5 min.
|
||||
- condition: template
|
||||
value_template: >-
|
||||
{{ states('input_datetime.pfv_ups_shutdown_last_page') in ['unknown', 'unavailable', 'none']
|
||||
or as_timestamp(now()) - as_timestamp(states('input_datetime.pfv_ups_shutdown_last_page')) > 21600 }}
|
||||
actions:
|
||||
- action: input_datetime.set_datetime
|
||||
target:
|
||||
entity_id: input_datetime.pfv_ups_shutdown_last_page
|
||||
data:
|
||||
datetime: "{{ now().strftime('%Y-%m-%d %H:%M:%S') }}"
|
||||
- variables:
|
||||
execute_mode: >-
|
||||
{{ is_state('input_boolean.pfv_ups_shutdown_armed', 'on')
|
||||
@@ -97,7 +114,8 @@ automation:
|
||||
(ca LAST — signing path for everything above)
|
||||
5. pfv-bms VM 100 LAST of the VMs — the brain stays up until now
|
||||
6. Hypervisors: iDRAC graceful off tsys6/tsys7 (PowerEdge);
|
||||
tsys1/3/4/5/9 idle out on UPS exhaustion (OptiPlex/Precision)
|
||||
tsys1, tsys3, tsys4, tsys5, tsys9 idle out on UPS exhaustion
|
||||
(OptiPlex/Precision, no BMC)
|
||||
mode_note: >-
|
||||
{{ 'MODE: EXECUTE (armed, live dispatch)' if execute_mode
|
||||
else 'MODE: DRY RUN (plan only — nothing will be shut down)' }}
|
||||
@@ -122,3 +140,10 @@ automation:
|
||||
data:
|
||||
title: "{{ 'UPS SHUTDOWN EXECUTING' if execute_mode else 'UPS SHUTDOWN PLAN (dry run)' }}"
|
||||
message: "{{ plan }}"
|
||||
# Suppression stamp set LAST — a failed notify must not suppress the
|
||||
# next 5-min re-page cycle.
|
||||
- action: input_datetime.set_datetime
|
||||
target:
|
||||
entity_id: input_datetime.pfv_ups_shutdown_last_page
|
||||
data:
|
||||
datetime: "{{ now().strftime('%Y-%m-%d %H:%M:%S') }}"
|
||||
|
||||
+16
-3
@@ -63,17 +63,30 @@ t "trend sensors fed from smoothed sources" \
|
||||
t "runtime-low covers Tripp Lite" \
|
||||
"sed -n '/id: pfv_plant_ups_runtime_low/,/^ mode:/p' automations.yaml | grep -q 'sensor.pfv_tripp_lite_runtime_minutes'"
|
||||
t "runtime-low status check maps per-UPS" \
|
||||
"sed -n '/id: pfv_plant_ups_runtime_low/,/^ mode:/p' automations.yaml | grep -q 'status_map'"
|
||||
"sed -n '/id: pfv_plant_ups_runtime_low/,/^ mode:/p' automations.yaml | grep -q \"sensor.pfv_tripp_lite_runtime_minutes', 'sensor.tsys1_triplite_status'\""
|
||||
|
||||
echo "=== UPS shutdown chain (#790 — dry-run is the shipped mode) ==="
|
||||
t "shutdown chain package present, dry-run default ON" \
|
||||
"grep -q 'id: pfv_ups_shutdown_plan' packages/ups_shutdown.yaml && grep -A4 'pfv_ups_shutdown_dry_run:' packages/ups_shutdown.yaml | grep -q 'initial: true'"
|
||||
t "armed switch default OFF" \
|
||||
"grep -A4 'pfv_ups_shutdown_armed:' packages/ups_shutdown.yaml | grep -q 'initial: false'"
|
||||
t "plan covers all seven hypervisors" \
|
||||
"for h in tsys1 tsys3 tsys4 tsys5 tsys6 tsys7 tsys9; do grep -q \$h packages/ups_shutdown.yaml || exit 1; done"
|
||||
# Host coverage must hold in the PLAN BODY, not the header comment —
|
||||
# scope the grep to the plan template variable.
|
||||
PLAN_OK=1
|
||||
for h in tsys1 tsys3 tsys4 tsys5 tsys6 tsys7 tsys9; do
|
||||
# full-read grep (not -q): the script runs with pipefail — -q's early
|
||||
# exit SIGPIPEs sed and flips the pipeline status to 141
|
||||
sed -n '/plan: >-/,/mode_note:/p' packages/ups_shutdown.yaml | grep "$h" >/dev/null || PLAN_OK=0
|
||||
done
|
||||
t "plan covers all seven hypervisors (plan body)" "[ \$PLAN_OK -eq 1 ]"
|
||||
t "pfv-bms VM 100 ordered last of the VMs (#455)" \
|
||||
"grep -q 'pfv-bms VM 100 LAST' packages/ups_shutdown.yaml"
|
||||
|
||||
echo "=== level-based re-checks (review finding: edge-only triggers miss pages) ==="
|
||||
t "runtime-low re-polls every 5 min" \
|
||||
"sed -n '/id: pfv_plant_ups_runtime_low/,/^ mode:/p' automations.yaml | grep -q 'minutes: /5'"
|
||||
t "shutdown chain re-polls every 5 min" \
|
||||
"grep -A30 'id: pfv_ups_shutdown_plan' packages/ups_shutdown.yaml | grep -q 'minutes: /5'"
|
||||
|
||||
echo "=== SDLC SUITE: $FAIL failures ==="
|
||||
exit "$FAIL"
|
||||
|
||||
Reference in New Issue
Block a user