Merge pull request 'URGENT hotfix: smoothed sensors + shutdown switches did not materialize in 996d54c' (#4) from dev into release
ci / lint (push) Successful in 1m6s
ci / lint (push) Successful in 1m6s
Reviewed-on: #4
This commit was merged in pull request #4.
This commit is contained in:
+30
-22
@@ -542,36 +542,44 @@ sensor:
|
||||
method: left
|
||||
unique_id: pfv_garage_pdu_energy
|
||||
|
||||
# --- Rate-of-change early warning (#682): +10°F/15min = AC trouble [#344] ---
|
||||
# DRAC sensors quantize to whole °C and FLAP ~1.8°F between polls; raw-fed
|
||||
# trend sensors false-tripped TEMP RISING FAST (2026-09-06 05:02 CDT, tsys6).
|
||||
# Trend inputs are 5-min time-weighted moving averages — real climbs survive
|
||||
# the smoothing, quantization flapping does not.
|
||||
filter:
|
||||
- platform: time_simple_moving_average
|
||||
# --- Smoothed ambient feeds for the trend sensors (2026-09-06) ---
|
||||
# DRAC sensors quantize to whole °C and FLAP ~1.8°F between polls; raw-fed
|
||||
# trend sensors false-tripped TEMP RISING FAST (05:02 CDT, tsys6). Trend
|
||||
# inputs are 5-min time-weighted moving averages (legacy filter SENSOR
|
||||
# platform — a top-level `filter:` key cannot be merged from packages).
|
||||
# Real climbs survive the smoothing, quantization flapping does not.
|
||||
- platform: filter
|
||||
name: "PFV tsys1 rack temperature smoothed"
|
||||
entity_id: sensor.pfv_tsys1_rack_temperature
|
||||
window: "00:05:00"
|
||||
precision: 2
|
||||
unique_id: pfv_tsys1_rack_temperature_smoothed
|
||||
- platform: time_simple_moving_average
|
||||
entity_id: sensor.pfv_tsys1_rack_temperature
|
||||
filters:
|
||||
- filter: time_simple_moving_average
|
||||
window: "00:05"
|
||||
precision: 2
|
||||
- platform: filter
|
||||
name: "PFV tsys6 DRAC ambient smoothed"
|
||||
entity_id: sensor.pfv_tsys6_drac_ambient
|
||||
window: "00:05:00"
|
||||
precision: 2
|
||||
unique_id: pfv_tsys6_drac_ambient_smoothed
|
||||
- platform: time_simple_moving_average
|
||||
entity_id: sensor.pfv_tsys6_drac_ambient
|
||||
filters:
|
||||
- filter: time_simple_moving_average
|
||||
window: "00:05"
|
||||
precision: 2
|
||||
- platform: filter
|
||||
name: "PFV tsys7 DRAC inlet smoothed"
|
||||
entity_id: sensor.pfv_tsys7_drac_inlet
|
||||
window: "00:05:00"
|
||||
precision: 2
|
||||
unique_id: pfv_tsys7_drac_inlet_smoothed
|
||||
- platform: time_simple_moving_average
|
||||
entity_id: sensor.pfv_tsys7_drac_inlet
|
||||
filters:
|
||||
- filter: time_simple_moving_average
|
||||
window: "00:05"
|
||||
precision: 2
|
||||
- platform: filter
|
||||
name: "PFV garage temperature smoothed"
|
||||
entity_id: sensor.pfv_garage_temperature
|
||||
window: "00:05:00"
|
||||
precision: 2
|
||||
unique_id: pfv_garage_temperature_smoothed
|
||||
entity_id: sensor.pfv_garage_temperature
|
||||
filters:
|
||||
- filter: time_simple_moving_average
|
||||
window: "00:05"
|
||||
precision: 2
|
||||
|
||||
binary_sensor:
|
||||
- platform: trend
|
||||
|
||||
@@ -24,14 +24,15 @@ input_boolean:
|
||||
# mid-test silently reverts these to the safe defaults (armed OFF,
|
||||
# dry-run ON). Safe direction, but re-arm after any restart during the
|
||||
# supervised Sept 11-12 live test.
|
||||
# (no description: keys — input_boolean rejects them, 2026-09-06)
|
||||
pfv_ups_shutdown_armed:
|
||||
# Founder arm. ON + dry-run OFF = real shutdown dispatch.
|
||||
name: UPS shutdown chain ARMED
|
||||
description: Founder-level arm. ON + dry-run OFF = real shutdown dispatch.
|
||||
icon: mdi:power-standby
|
||||
initial: false
|
||||
pfv_ups_shutdown_dry_run:
|
||||
# ON (default) = log/page the plan only, touch nothing.
|
||||
name: UPS shutdown DRY RUN
|
||||
description: ON (default) = log/page the plan only, touch nothing.
|
||||
icon: mdi:numeric-1-box-outline
|
||||
initial: true
|
||||
|
||||
|
||||
Reference in New Issue